• Parameters
MODE
ITEM
SETTING PARAMETER
RANGE
UNIT
INITIAL VALUE
Ch4 Setting
01
Lockout setting
Lock / Unlock
–
Lock
302
Ch4 Enable
Disable / Enable
–
Enable
311
Ch4 Input range
0 – 20 mA
-5 – +5 V
-10 – +10 V
–
-5 – +5 V
312
Ch4 0% Input setting
0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
1.000
313
Ch4 100 % Input setting
1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
5.000
314
Ch4 0 % Input scaling
-99999 – 999999
–
0.00
315
Ch4 100 % Input scaling
-99999 – 999999
–
100.00
316
Ch4 Input decimal point
No decimal point
The number of decimal places: 1 – 5
–
2 places of decimals
317
Ch4 Unit (INP Scaling)
Choose from 68 types
–
%
361
Ch4 Output range
0 – 20 mA
-5 – +5 V
-10 – +10 V
–
0 – 20 mA
362
Ch4 0 % Output setting
0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
4.000
363
Ch4 100 % Output setting
1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
20.000
371
Ch4 Filter time constant
0 – 30
sec.
0
381
Ch4 Input zero fine adjust
-5.000 – 5.000
%
0.000
382
Ch4 Input span fine adjust
95.000 – 105.000
%
100.000
391
Ch4 Output zero fine adjust
-5.000 – 5.000
%
0.000
392
Ch4 Output span fine adjust
95.000 – 105.000
%
100.000
395
Ch4 User’s table linearization Cancel / Set
–
Cancel
398
Ch4 Loop test
-5.00 – 105.00
%
Cancel
[01] Lockout setting
Enable / disable Lockout setting.
SETTING VALUE DESCRIPTION
INITIAL VALUE
Lock
Enable Lockout setting
Lock
Unlock
Disable Lockout setting
When Lockout setting is enabled, it is possible to shift to
each setting mode and confirm the setting value of each
setting parameter item. Each parameter item display in-
dicates ‘DATA (Locked)’ when set to ‘Lock’, and indicates
‘DATA’ when set to ‘Unlock’.
[302] Ch4 Enable
Enable / disable Ch4.
No output signal or present value is displayed for the disa-
bled channel in Measuring Mode.
SETTING VALUE DESCRIPTION
INITIAL VALUE
Disable
Ch4 Disable
Enable
Enable
Ch4 Enable
Even when Ch4 is disabled, parameter settings for Ch4 can
be performed.
[311] Ch4 Input range
Set the input range.
SETTING VALUE DESCRIPTION
INITIAL VALUE
0 – 20 mA
Input: 0 – 20 mA DC
-5 – +5 V
-5 – +5 V
Input: -5 – +5 V DC
-10 – +10 V
Input: -10 – +10 V DC
When the input range is changed, turn the power off, and
change the connection to the input terminal of the unit ac-
cordingly. Note that input setting values are changed to the
initial values.
[312] Ch4 0 % Input setting
Set the 0 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
0.00 – 19.00
1.00
4.00
-5 – +5 V
-5.000 – 4.750
0.250
1.000
-10 – +10 V
-10.000 – 9.000
1.000
-10.000
Set as follows.
[312] 0 % input setting < [313] 100 % input setting
[313] Ch4 100 % Input setting
Set the 100 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
1.00 – 20.00
1.00
20.00
-5 – +5 V
-4.750 – 5.000
0.250
5.000
-10 – +10 V
-9.000 – 10.000
1.000
10.000
Set as follows.
[312] 0 % input setting < [313] 100 % input setting
[314] Ch4 0 % Input scaling
Set the display value of 0 % input setting.
SETTING RANGE
INITIAL VALUE
-99999 – 999999
0.00
[315] Ch4 100 % Input scaling
Set the display value of 100 % input setting.
SETTING RANGE
INITIAL VALUE
-99999 – 999999
100.00