EM-6040-B  Rev.2  P. 22 / 37

• Parameters

MODE

ITEM

SETTING PARAMETER

RANGE

UNIT

INITIAL VALUE

Ch4 Setting

01

Lockout setting

Lock / Unlock

Lock

302

Ch4 Enable

Disable / Enable

Enable

311

Ch4 Input range

0 – 20 mA
-5 – +5 V
-10 – +10 V

-5 – +5 V

312

Ch4 0% Input setting

0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000

mA

V
V

1.000

313

Ch4 100 % Input setting

1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000

mA

V
V

5.000

314

Ch4 0 % Input scaling

-99999 – 999999

0.00

315

Ch4 100 % Input scaling

-99999 – 999999

100.00

316

Ch4 Input decimal point

No decimal point
The number of decimal places: 1 – 5

2 places of decimals

317

Ch4 Unit (INP Scaling)

Choose from 68 types

%

361

Ch4 Output range

0 – 20 mA
-5 – +5 V
-10 – +10 V

0 – 20 mA

362

Ch4 0 % Output setting

0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000

mA

V
V

4.000

363

Ch4 100 % Output setting

1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000

mA

V
V

20.000

371

Ch4 Filter time constant

0 – 30

sec.

0

381

Ch4 Input zero fine adjust

-5.000 – 5.000

%

0.000

382

Ch4 Input span fine adjust

95.000 – 105.000

%

100.000

391

Ch4 Output zero fine adjust

-5.000 – 5.000

%

0.000

392

Ch4 Output span fine adjust

95.000 – 105.000

%

100.000

395

Ch4 User’s table linearization Cancel / Set

Cancel

398

Ch4 Loop test

-5.00 – 105.00

%

Cancel

[01] Lockout setting

Enable / disable Lockout setting.

SETTING VALUE DESCRIPTION

INITIAL VALUE

Lock

Enable Lockout setting 

Lock

Unlock

Disable Lockout setting 

When Lockout setting is enabled, it is possible to shift to 
each setting mode and confirm the setting value of each 
setting parameter item.  Each parameter item display in-
dicates ‘DATA (Locked)’ when set to ‘Lock’, and indicates 
‘DATA’ when set to ‘Unlock’.

[302] Ch4 Enable

Enable / disable Ch4.
No output signal or present value is displayed for the disa-
bled channel in Measuring Mode.

SETTING VALUE DESCRIPTION

INITIAL VALUE

Disable

Ch4 Disable

Enable

Enable

Ch4 Enable

Even when Ch4 is disabled, parameter settings for Ch4 can 
be performed.

[311] Ch4 Input range

Set the input range.

SETTING VALUE DESCRIPTION

INITIAL VALUE

0 – 20 mA

Input: 0 – 20 mA DC

-5 – +5 V

-5 – +5 V

Input: -5 – +5 V DC

-10 – +10 V

Input: -10 – +10 V DC

When the input range is changed, turn the power off, and 
change the connection to the input terminal of the unit ac-
cordingly.  Note that input setting values are changed to the 
initial values.

[312] Ch4 0 % Input setting

Set the 0 % input setting value.
Setting range differs according to input range.

INPUT RANGE

SETTING RANGE MIN. SPAN INITIAL VALUE

0 – 20 mA

0.00 – 19.00

1.00

4.00

-5 – +5 V

-5.000 – 4.750

0.250

1.000

-10 – +10 V

-10.000 – 9.000

1.000

-10.000

Set as follows.
[312] 0 % input setting < [313] 100 % input setting

[313] Ch4 100 % Input setting

Set the 100 % input setting value.
Setting range differs according to input range.

INPUT RANGE

SETTING RANGE MIN. SPAN INITIAL VALUE

0 – 20 mA

1.00 – 20.00

1.00

20.00

-5 – +5 V

-4.750 – 5.000

0.250

5.000

-10 – +10 V

-9.000 – 10.000

1.000

10.000

Set as follows.
[312] 0 % input setting < [313] 100 % input setting

[314] Ch4 0 % Input scaling

Set the display value of 0 % input setting.

SETTING RANGE

INITIAL VALUE

-99999 – 999999

0.00

[315] Ch4 100 % Input scaling

Set the display value of 100 % input setting.

SETTING RANGE

INITIAL VALUE

-99999 – 999999

100.00

Содержание M1EXV-4

Страница 1: ...37 OPERATING MANUAL SIGNAL TRANSMITTER 4 channel PC programmable MODEL M1EXV 4 CONTENTS BEFORE USE 2 POINTS OF CAUTION 2 COMPONENT IDENTIFICATION 3 INSTALLATION 3 TERMINAL CONNECTIONS 4 EXTERNAL VIEW...

Страница 2: ...ensure the CE conform ity Install lightning surge protectors for those wires connect ed to remote locations POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and...

Страница 3: ...Unused 18 Ch4 Output 9 Ch2 Input 19 Power 10 Ch2 Input 20 Power INSTALLATION The unit can be removed from the base by pulling out while pressing the lockslider on the top thereof The base does not com...

Страница 4: ...inch 125 4 92 36 1 42 89 3 50 5 20 5 20 7 28 7 28 45 1 77 4 16 DIN RAIL 35mm wide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Base does not come with the unit Please order separately MOUNTING...

Страница 5: ...de pressing Mode button shift to the setting mode for the next channel Pressing Mode button for 2 seconds returns to Measuring mode from each setting mode In Measuring mode shortly pressing the button...

Страница 6: ...NPUT V 1 00 4 00 Ch1 OUTPUT mA Ch2 INPUT V 1 00 4 00 Ch2 OUTPUT mA Ch3 INPUT V 1 00 4 00 Ch3 OUTPUT mA Ch4 INPUT V 1 00 4 00 Ch4 OUTPUT mA Mode button Mode button Mode button Mode button DISPLAY IN EA...

Страница 7: ...Setting Mode Ch4 Setting Mode Advanced Mode Hold down Mode button for 1 5 seconds Hold down Mode button for 2 seconds Hold down Mode button for 3 seconds Hold down Mode button for 2 seconds Hold down...

Страница 8: ...ng change press Down button to select the setting value or decrease the numerical value Keeping pressing Down button decreases the value continuously Note DO NOT press 2 or more buttons simultaneously...

Страница 9: ...999 oooooo ooooo o oooo oo ooo ooo oo oooo o ooooo 1 000 20 000 4 750 5 000 9 000 10 000 0 20 mA 5 5 V 10 10 V 0 000 19 000 5 000 4 750 10 000 9 000 1 000 20 000 4 750 5 000 9 000 10 000 Up Down Up Do...

Страница 10: ...possible to shift to each setting mode and confirm the setting value of each setting parameter item Each parameter item display in dicates DATA Locked when set to Lock and indicates DATA when set to...

Страница 11: ...NPUT Scaling in Measur ing mode Initial value 1 Settable characters 0 9 A Z a z _ 61 Ch1 Output range Set the range of output signal of the unit SETTING VALUE DESCRIPTION INITIAL VALUE 0 20 mA Output...

Страница 12: ...ation Ch1 Linearization enable 98 Ch1 Loop test Output signal can be simulated for performing loop test Press Set button and confirm that Cancel is displayed with blinking Press Up or Down button to c...

Страница 13: ...9999 oooooo ooooo o oooo oo ooo ooo oo oooo o ooooo 1 000 20 000 4 750 5 000 9 000 10 000 0 20 mA 5 5 V 10 10 V 0 000 19 000 5 000 4 750 10 000 9 000 1 000 20 000 4 750 5 000 9 000 10 000 Up Down Up D...

Страница 14: ...t is possible to shift to each setting mode and confirm the setting value of each setting parameter item Each parameter item display in dicates DATA Locked when set to Lock and indicates DATA when set...

Страница 15: ...ling in Measur ing mode Initial value 1 Settable characters 0 9 A Z a z _ 161 Ch2 Output range Set the range of output signal of the unit SETTING VALUE DESCRIPTION INITIAL VALUE 0 20 mA Output 0 20 mA...

Страница 16: ...ation Ch2 Linearization enable 198 Ch2 Loop test Output signal can be simulated for performing loop test Press Set button and confirm that Cancel is displayed with blinking Press Up or Down button to...

Страница 17: ...9999 oooooo ooooo o oooo oo ooo ooo oo oooo o ooooo 1 000 20 000 4 750 5 000 9 000 10 000 0 20 mA 5 5 V 10 10 V 0 000 19 000 5 000 4 750 10 000 9 000 1 000 20 000 4 750 5 000 9 000 10 000 Up Down Up D...

Страница 18: ...t is possible to shift to each setting mode and confirm the setting value of each setting parameter item Each parameter item display in dicates DATA Locked when set to Lock and indicates DATA when set...

Страница 19: ...T Scaling in Measur ing mode Initial value 1 Settable characters 0 9 A Z a z _ 261 Ch3 Output range Set the range of output signal of the unit SETTING VALUE DESCRIPTION INITIAL VALUE 0 20 mA Output 0...

Страница 20: ...ation Ch3 Linearization enable 298 Ch3 Loop test Output signal can be simulated for performing loop test Press Set button and confirm that Cancel is displayed with blinking Press Up or Down button to...

Страница 21: ...9999 oooooo ooooo o oooo oo ooo ooo oo oooo o ooooo 1 000 20 000 4 750 5 000 9 000 10 000 0 20 mA 5 5 V 10 10 V 0 000 19 000 5 000 4 750 10 000 9 000 1 000 20 000 4 750 5 000 9 000 10 000 Up Down Up D...

Страница 22: ...t is possible to shift to each setting mode and confirm the setting value of each setting parameter item Each parameter item display in dicates DATA Locked when set to Lock and indicates DATA when set...

Страница 23: ...T Scaling in Measur ing mode Initial value 1 Settable characters 0 9 A Z a z _ 361 Ch4 Output range Set the range of output signal of the unit SETTING VALUE DESCRIPTION INITIAL VALUE 0 20 mA Output 0...

Страница 24: ...ation Ch4 Linearization enable 398 Ch4 Loop test Output signal can be simulated for performing loop test Press Set button and confirm that Cancel is displayed with blinking Press Up or Down button to...

Страница 25: ...seconds Hold down Mode button for 2 seconds Advanced Mode Parameters MODE ITEM SETTING PARAMETER RANGE UNIT INITIAL VALUE Advanced 01 Lockout setting Lock Unlock Lock 401 Display1 setting Upper choos...

Страница 26: ...ineering unit value Ch2 INPUT Ch2 Input engineering unit value Ch2 INPUT Scaling 1 Ch2 Input scaling Ch2 PERCENT Ch2 Percent value 2 Ch2 OUTPUT Ch2 Output engineering unit value Ch3 INPUT Ch3 Input en...

Страница 27: ...period to turn off the display when there is no operation within a certain time period Settable range 0 60 minutes To keep the display always on set to 0 When an error occurs at display off the displa...

Страница 28: ...et Up Down Up Down Up Down Up Down Up Down Up Down Up Down Disable Enable 2 111 5 00 105 00 5 00 105 00 5 00 105 00 5 00 105 00 ITEM 95 User s Table Linearization Ch1 Linearization Mode Table X001 Tab...

Страница 29: ...ues of X corresponding to input unit and values of Y corresponding to output unit are paired respectively The table is searched for an X value that matches the input to be converted and a Y value pair...

Страница 30: ...Up Down Up Down Up Down Up Down Up Down Up Down Up Down Disable Enable 2 111 5 00 105 00 5 00 105 00 5 00 105 00 5 00 105 00 ITEM 195 User s Table Linearization Ch2 Linearization Mode Table X001 Tabl...

Страница 31: ...alues of X corresponding to input unit and values of Y corresponding to output unit are paired respectively The table is searched for an X value that matches the input to be converted and a Y value pa...

Страница 32: ...Up Down Up Down Up Down Up Down Up Down Up Down Up Down Disable Enable 2 111 5 00 105 00 5 00 105 00 5 00 105 00 5 00 105 00 ITEM 295 User s Table Linearization Ch3 Linearization Mode Table X001 Tabl...

Страница 33: ...alues of X corresponding to input unit and values of Y corresponding to output unit are paired respectively The table is searched for an X value that matches the input to be converted and a Y value pa...

Страница 34: ...Up Down Up Down Up Down Up Down Up Down Up Down Up Down Disable Enable 2 111 5 00 105 00 5 00 105 00 5 00 105 00 5 00 105 00 ITEM 395 User s Table Linearization Ch4 Linearization Mode Table X001 Tabl...

Страница 35: ...alues of X corresponding to input unit and values of Y corresponding to output unit are paired respectively The table is searched for an X value that matches the input to be converted and a Y value pa...

Страница 36: ...of display setting Error is indicated with blinking at the upper or lower part of the display When multiple errors occur only the highest priority error is displayed The order of priority is EEPROM ER...

Страница 37: ...eferring to the M1ECFG users manual EM 5981 when adjusting with M1E Configurator Software model M1ECFG INPUT FINE ADJUSTMENT 1 Set the input signal to 0 and adjust the displayed in put value to 0 by 8...

Отзывы: