• Parameters
MODE
ITEM
SETTING PARAMETER
RANGE
UNIT
INITIAL VALUE
Ch1 Setting
01
Lockout setting
Lock / Unlock
–
Lock
02
Ch1 Enable
Disable / Enable
–
Enable
11
Ch1 Input range
0 – 20 mA
-5 – +5 V
-10 – +10 V
–
-5 – +5 V
12
Ch1 0% Input setting
0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
1.000
13
Ch1 100 % Input setting
1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
5.000
14
Ch1 0 % Input scaling
-99999 – 999999
–
0.00
15
Ch1 100 % Input scaling
-99999 – 999999
–
100.00
16
Ch1 Input decimal point
No decimal point
The number of decimal places: 1 – 5
–
2 places of decimals
17
Ch1 Unit (INP Scaling)
Choose from 68 types
–
%
61
Ch1 Output range
0 – 20 mA
-5 – +5 V
-10 – +10 V
–
0 – 20 mA
62
Ch1 0 % Output setting
0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
4.000
63
Ch1 100 % Output setting
1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
20.000
71
Ch1 Filter time constant
0 – 30
sec.
0
81
Ch1 Input zero fine adjust
-5.000 – 5.000
%
0.000
82
Ch1 Input span fine adjust
95.000 – 105.000
%
100.000
91
Ch1 Output zero fine adjust
-5.000 – 5.000
%
0.000
92
Ch1 Output span fine adjust
95.000 – 105.000
%
100.000
95
Ch1 User’s table linearization Cancel / Set
–
Cancel
98
Ch1 Loop test
-5.00 – 105.00
%
Cancel
[01] Lockout setting
Enable / disable Lockout setting.
SETTING VALUE DESCRIPTION
INITIAL VALUE
Lock
Enable Lockout setting
Lock
Unlock
Disable Lockout setting
When Lockout setting is enabled, it is possible to shift to
each setting mode and confirm the setting value of each
setting parameter item. Each parameter item display in-
dicates ‘DATA (Locked)’ when set to ‘Lock’, and indicates
‘DATA’ when set to ‘Unlock’.
[02] Ch1 Enable
Enable / disable Ch1.
No output signal or present value is displayed for the disa-
bled channel in Measuring Mode.
SETTING VALUE DESCRIPTION
INITIAL VALUE
Disable
Disable Ch1
Enable
Enable
Enable Ch1
Even when Ch1 is disabled, parameter settings for Ch1 can
be performed.
[11] Ch1 Input range
Set the input range.
SETTING VALUE DESCRIPTION
INITIAL VALUE
0 – 20 mA
Input: 0 – 20 mA DC
-5 – +5 V
-5 – +5 V
Input: -5 – +5 V DC
-10 – +10 V
Input: -10 – +10 V DC
When the input range is changed, turn the power off, and
change the connection to the input terminal of the unit ac-
cordingly. Note that input setting values are changed to the
initial values.
[12] Ch1 0 % Input setting
Set the 0 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
0.00 – 19.00
1.00
4.00
-5 – +5 V
-5.000 – 4.750
0.250
1.000
-10 – +10 V
-10.000 – 9.000
1.000
-10.000
Set as follows.
[12] 0 % input setting < [13] 100 % input setting
[13] Ch1 100 % Input setting
Set the 100 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE MIN. SPAN INITIAL VALUE
0 – 20 mA
1.00 – 20.00
1.00
20.00
-5 – +5 V
-4.750 – 5.000
0.250
5.000
-10 – +10 V
-9.000 – 10.000
1.000
10.000
Set as follows.
[12] 0 % input setting < [13] 100 % input setting
[14] Ch1 0 % Input scaling
Set the display value of 0 % input setting
.
SETTING RANGE
INITIAL VALUE
-99999 – 999999
0.00
[15] Ch1 100 % Input scaling
Set the display value of 100 % input setting.
SETTING RANGE
INITIAL VALUE
-99999 – 999999
100.00