R7I4DECT-1-PA8A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7779-F Rev.1 P. 11 / 11
I/O DATA DESCRIPTIONS
■
TOTALIZED PULSE INPUT MODULE (R7I4DECT-1-PA8A)
•
Input Area Objects
0
15
16
31
32-bit binary data
When the channel is invalid, the pulse count is fixed to 0.
Accumulated pulse count (upper 16 bits)
Accumulated pulse count (lower 16 bits)
OUTPUT DATA n+0
•
Output Area Objects
0
15
CH0 Pulse count reset bit
CH1 Pulse count reset bit
CH2 Pulse count reset bit
CH3 Pulse count reset bit
CH7 Pulse count reset bit
CH4 Pulse count reset bit
CH5 Pulse count reset bit
CH6 Pulse count reset bit
Unused
0
15
16
31
Preset value (upper 16 bits)
Preset value (lower 16 bits)
OUTPUT DATA n+1
0
15
OUTPUT DATA n+2
CH0 Pulse count preset bit
CH1 Pulse count preset bit
CH2 Pulse count preset bit
CH3 Pulse count preset bit
CH7 Pulse count preset bit
CH4 Pulse count preset bit
CH5 Pulse count preset bit
CH6 Pulse count preset bit
Unused
■
PULSE COUNT RESET
In n+0 word of the output data from host PC/PLC, the bits to reset the totalized values of the respective channels are allocated.
By changing the bits from 0 to 1, the totalized values of the respective channels are reset.
Confirm that the totalized values are reset, and return the bits to 0.
Note that the next reset will not work if the reset bits remain at 1.
■
PULSE COUNT PRESET
Write the desired preset values in n+2 word and n+3 word of the output data from host PC/PLC.
The bits to preset the totalized values of the respective channels are allocated in n+1 word.
By changing the bits from 0 to 1, the preset values are reflected to the totalized values of the respective channels.
Confirm that the totalized values are preset, and return the bits to 0.