14
47D Series Modbus Reference Guide EM-9501-C Rev.4
3.5.5 RTD INPUT
R
ADDR. WORD CONTENTS
UNIT
1051
1
Input type
0 : JPt 100 (JIS ’89)
1 : Pt 100 (JIS ’89)
2 : Pt 100 (JIS ’97, IEC) (*)
3 : Pt 50 (JIS ’81)
4 : Pt 1000
1052
1
Temperature unit
0 : °C (*)
1 : °F
1063
1
Burnout
0 : Downscale
1 : Upscale (*)
1065
2
Input compensation A input value *
5
°C/100
-99999 ... 999999
or
Factory setting : 000
°F/100
1067
2
Input compensation B input value *
5
°C/100
-99999 ... 999999
or
Factory setting : 8000
°F/100
1069
2
Input compensation A compensation value
°C/100
-99999 ... 999999
or
Factory setting : 0
°F/100
1071
2
Input compensation B compensation value
°C/100
-99999 ... 999999
or
Factory setting : 0
°F/100
*5. Input compensation is not executed when the A and B values are equal.
3.5.6 THERMOCOUPLE INPUT
T
ADDR. WORD CONTENTS
UNIT
1051
1
Input type
0 : (PR)
1 : K (CA) 1 (*)
2 : K (CA) 2
3 : E (CRC)
4 : J (IC) 1
5 : J (IC) 2
6 : T (CC)
7 : B (RH)
8 : R
9 : S
10 : C (WRe5-26)
11 : N
12 : U
13 : L
1052
1
Temperature unit
0 : °C (*)
1 : °F
1063
1
Burnout
0 : Downscale
1 : Upscale (*)
1064
1
Cold junction compensation
0 : ON (*)
1 : OFF
1065
2
Input compensation A input value *
5
°C/100
-99999 ... 999999
or
Factory setting : 000
°F/100
1067
2
Input compensation B input value *
5
°C/100
-99999 ... 999999
or
Factory setting : 100000
°F/100
1069
2
Input compensation A compensation value
°C/100
-99999 ... 999999
or
Factory setting : 0
°F/100
1071
2
Input compensation B compensation value
°C/100
-99999 ... 999999
or
Factory setting : 0
°F/100
*5. Input compensation is not executed when the A and B values are equal.