47D Series Modbus Reference Guide EM-9501-C Rev.4
3.6 BARGRAPH SETTING
ADDR. WORD CONTENTS
2001
1
Bargraph type
0 : No bargraph indication
1 : Unidirectional bar (*)
2 : Unidirectional bar, reverse LCD
3 : Bidirectional bar
4 : Bidirectional bar, reverse LCD
2002
2
Bargraph lower limit
-20000 ... 100000
V M AC V M AC
Decimal point position setting
-99999 ... 999999
T R
T R
°C/100 or °F/100
Factory setting :
VV
10000 /
VA
04000 /
T
0 /
R
0 /
M
-10000 /
AC
000000/000000
2004
2
Bargraph upper limit
-20000 ... 100000
V M AC V M AC
Decimal point position setting
-99999 ... 999999
T R
T R
°C/100 or °F/100
Factory setting :
VV
50000 /
VA
20000 /
T
10000 /
R
10000 /
M
10000 /
AC
020000/020000
3.7 ANALOG OUTPUT SETTING
ADDR. WORD CONTENTS
UNIT
3001
1
Analog output type
0 : 0 to 5V
1 : -5 to +5V
2 : -10 to +10V
3 : 0 to 20mA
4 : 4 to 20mA (*)
3002
1
Analog output function mode
0 : Proportional to the display value (*)
1 : Proportional to the scaling/temperature value
3003
2
Analog output 0%
-20000 ... 100000
V M
AC
V M AC
Decimal point position setting
-99999 ... 999999
T R
T R
°C/100 or °F/100
Factory setting :
VV
10000 /
VA
04000 /
T
0 /
R
0 /
M
-10000 /
AC
000000/000000
3005
2
Analog output 100%
-20000 ... 100000
V M AC
V M AC
Decimal point position setting
-99999 ... 999999
T R
T R
°C/100 or °F/100
Factory setting :
VV
50000 /
VA
20000 /
T
10000 /
R
10000 /
M
10000 /
AC
020000/020000
3007
2
Analog output 0% adjustment
%/1000
-5000 ... 100000
0% adjustment value ≤ 100% adjustment value – 5000
Factory setting : 0
3009
2
Analog output 100% adjustment
%/1000
0 ... 105000
0% adjustment value + 5000 ≤ 100% adjustment value
Factory setting : 100000