CARE & USE/INSTALLATION
|
9
CLEARANCE TO CONSTRUCTION
STRAIGHT MOUNTING
If the heater is to be mounted facing straight down with no angle on its pivot point, then the heater
must be mounted NO CLOSER than 14” from any overhead combustible construction. The side
clearances must be NO CLOSER than 12” to a side wall, and the rear clearances must be NO CLOSER
than 12” to a rear wall. Use the LOWEST pair of holes in the mounting bracket extension arms. See
illustration below.
ANGLED MOUNTING
If the heater is to be mounted at an angle up to 30 degrees on its pivot, then the heater must be
mounted NO CLOSER than 18” from any overhead combustible construction. The side clearances
must be NO CLOSER than 12” to a side wall, and the rear clearances must be NO CLOSER than 12”
to a rear wall. Use the HIGHEST pair of holes in the mounting bracket extension arms. See illustration
below.