Electrical installation
Description of connection sockets
24
© Lutz-Jesco GmbH 2017
BA-10010-02-V01
Solenoid-diaphragm dosing pump
MAGDOS LA / LD
Operating instructions
9.2.1.3 Pulse input (only LD)
The pulse input makes it possible to control the delivery capacity by
means of pulses. The system regulates the delivery capacity by means of
the dosing pump's stroke frequency and number of strokes in depend-
ence on the number of pulses and the pulse spacing.
n
Provided potential-free contact
n
For potential-free NO contact, e.g. a contact-type water meter
n
5 V DC supply voltage (current across all connections limited to a total
maximum of 50 mA)
n
Pulse length min. 4 ms
Pin
M12x1
(A-coded)
Assignments
Connection
Cable colour
1
Pulses
1
3
Brown
BN
2
3
Ground (GND)
Blue
BU
4
-
-
-
Black
BK
Table 18: Connection port 2 - pulse input
* Applies to cable colours of cables from Lutz-Jesco GmbH. No liability is
accepted for cables from other manufacturers.
9.2.2 Connection socket 3
Level input
Connection port 3 serves the level monitoring of a dosing tank (e.g. a
suction line with a level switch).
n
5 V DC supply voltage (current across all connections limited to a total
maximum of 50 mA)
n
Alert and main alarm
n
Potential-free contact
n
Programmable NC or NO contact
i
A matching connection cable with A-coded plug connector is
integrated in the suction lines / level monitoring systems of
Lutz-Jesco GmbH. An adapter is required if using older suction
lines with a 3.5 mm jack plug. You can find this adapter and
additional cables in the Lutz-Jesco GmbH price list.
Pin
M12x1
(A-coded)
Assignments
Connection
Cable colour
1
Low level alert
3
2
1
Brown
BN
2
Main alarm
White
WH
3
Ground (GND)
Blue
BU
4
-
-
-
Black
BK
Table 19: Connection socket 3
* Applies to cable colours of cables from Lutz-Jesco GmbH. No liability is
accepted for cables from other manufacturers.
Removing the conductive rubber band
Fig. 19: Conductive rubber band in connection socket 3
Remove the conductive rubber band before inserting the cable in the
connection socket.
After the cable has been removed, the conductive rubber band must be
reinserted in the connection socket. Insert it between pins 1+2 and 3+4
as shown in Fig. 19.