7
7
Occupant Copy
Installation Instructions
EDU Assignment
Note:
Entering Assignment mode will cause the
window treatments to move between their Open and
Close limits.
Be sure that the Open and Close
limits have been set appropriately.
Note:
For the SQE-RL, use the
and
buttons instead of
the and buttons.
1. If using the SQE-33, select the group you wish to assign.
2. Enter Programming mode on the Keypad by pressing and
holding the Open (
) and Close (
) buttons
simultaneously for 5 seconds. The LEDs next to the Open
(
) and Close (
) buttons will flash once per second,
indicating the Keypad is in Programming mode.
3. Initiate Assignment mode by tapping the Close (
) button.
The LED next to the Close (
) button will continue to flash
(once per second) and the LED next to the Open (
)
button will turn off. EDUs that are assigned to the Keypad in
Assignment Mode will move to their Close limit. EDUs that
are not assigned to the Keypad will move to their Open
limit.
4. Tap any button on an EDU to toggle between assignment
or unassignment with the Keypad.
OR
Use the Open (
) button to step through each EDU in the
system. Each time the Open (
) button is tapped, a
window treatment will begin opening and closing over
approximately 200 mm (8 in). Repeat tapping the Open
(
) button until the desired EDU is selected. The Close
(
) button can also be used to select EDUs in the
opposite order.
5. Assign or unassign the currently selected EDU using the
Raise (
) and Lower (
) buttons. To assign, tap the
Lower (
) button. To unassign, tap the Raise (
)
button.
6. Check assignment before exiting Assignment mode. EDUs
that are at the Close limit are assigned. EDUs that are at
the Open limit are unassigned.
7. Exit Assignment mode by pressing and holding the Open
(
) and Close (
) button simultaneously for 5 seconds.
Each EDU will return to the level it was at when
Assignment mode was entered. The Open (
) and Close
(
) LEDs will stop flashing.
Press the Open (
)
and Close (
)
buttons
simultaneously for 5
seconds.
Flashing
once per
second
Tap the Close (
)
button.
Flashing
once per
second
Tap the Raise (
)
or Lower (
)
button.