Mounting 

Find a suitable location for mounting. 

•  Decide on the proper location for the GRX-TVI (NEMA Type 1 
  enclosure, indoor use only).

•  The environment where the GRX-TVI is placed must have an 

  ambient temperature range of 32 to 104 °F (0 to 40 °C). 

•   Mount the enclosure vertically on a wall (screws not provided). 

•  Mounting method must be able to support weight and forces 

applied during installation. 

•  Internal relays will click while in operation — mount where 

audible noise is acceptable.

 

Warning - Shock Hazard.

 To avoid the risk of electric shock, 

locate and remove fuse or lock circuit breaker in the OFF 
position before proceeding. Wiring with the power ON could 
result in personal injury or death.

Diameter - 0.25 in. (6mm)

Four Screws

Secure Cover

6.10 in.

(155 mm)

3.30 in.

(84 mm)

12.50 in.

(318 mm)

Wall

11.75 in.

(298 mm)

4.0 in.

(102 mm)

Mounting Diagram

Four Mounting Holes 
Diameter: 0.25 in (6 mm)

Four Screws Secure Cover

11.25 in

(298 mm)

12.50 in

(318 mm)

4.00 in

(102 mm)

6.10 in

(155 mm)

3.30 in

(84 mm)

WALL

N

2

DL

2

/DH

2

L

1

/H

100-277 V

~

N

1

SL

1

/SH

1

0-10 V

olt

-

L

2

/H

2

100-277 V

~

Wiring

1. Turn power off at fuse box or circuit breaker

 

Note:

 Multiple power feeds could be provided. Ensure that all feeds 

are off before wiring.

2. Wire control per appropriate wiring diagram (see next page) 

using wire connectors provided. Dots on diagrams represent wire 
connectors.

• 

Wiring Diagram A

 shows a GRX-TVI wired from one distribution 

panel. If the power requirement of the complete system is less than 
an MCB/circuit breaker rating and L1/H1 and L2/H2 are both coming 
from the same phase, one feed can be jumpered inside the enclosure 
(as shown on Page 3).  

• 

Wiring Diagram B

 shows a GRX-TVI wired from two separate 

distribution panels that may be different phases or voltages.  

•  Use the internal terminal block label to see where to land wires. 

  - The label shows two separate 

Line/Hot terminals (L1/H1 & 
L2/H2). L1/H1 is the Line/Hot feed 
to power the lighting load. 

  L2/H2 is the Line/Hot feed that 

powers internal circuitry of the
GRX-TVI.  

 Note 

1:

 Not all terminal blocks are 

required to have a connection for 
proper operation. 

 Note 

2:

 The power feed to the Control Unit (DL2/DH2) and L2/H2 of 

the GRX-TVI must be the same phase! 

 
  Class 2/PELV, 0-10 V

-

 wiring from a ballast/driver to the 

GRX-TVI must be separated from the power wiring. Enter the  Class 
2/PELV wires through the knockout adjacent to the 0-10 V

-

 terminal 

blocks. The barrier ensures separation and is fl exible to allow access 
to the terminals. The barrier must be in place when installation is 
complete. 

  GRX-TVI Internal Terminal Block Label Defi nitions 

 

L2/H2 100-277 V

~

Power input for GRX-TVI control 
(line voltage could be any voltage from 
100-277 V

~

)

. Refer to 

Note

 at the end of 

page 1.

N2

Neutral for GRX-TVI control

DL2/DH2

Control feed from the control unit

L1/H1 100-277 V

~

Power input for lighting load

N1

Neutral for lighting load (2 terminals 
provided and internally tied together — one 
for input neutral and one for load neutral)

SL1/SH1

Switched output to power lighting load

+/- 0-10 V

-

0-10 V

-

 control signal wires (ballast/driver  

must provide a 0-10 V

-

 source only)

Содержание Grafik Eye GRX-TVI

Страница 1: ...ode 10 A 16 A Motors 5 A 230 V CE 1 2 HP 100 120V 11 2 HP 200 277 V P N 032443 Rev A Important Installation Information Install in accordance with all national and local electrical codes Check for sho...

Страница 2: ...of the complete system is less than an MCB circuit breaker rating and L1 H1 and L2 H2 are both coming from the same phase one feed can be jumpered inside the enclosure as shown on Page 3 Wiring Diagr...

Страница 3: ...ONS Switched Line Hot Line Hot Line Hot Line Hot 0 10 V Ballast Driver 0 10 V Ballast Driver Earth Ground Earth Ground NOTICE 0 10 V Control Signal Wires DO NOT CONNECT TO LINE VOLTAGE LutronR is not...

Страница 4: ...connection is actually wired to a phase control input LED is not illuminated No Power Input Check that power is applied to the interface Limited Warranty Lutron will at its option repair or replace an...

Страница 5: ...r de acuerdo con todas las reglamentaciones de los c digos el ctricos nacionales y locales Veri que que no haya corto circuitos en las instalaciones nuevas antes de realizar el cableado del GRX TVI AD...

Страница 6: ...muestra una interfaz GRX TVI cableada desde dos paneles de distribuci n separados que pueden tener fases o voltajes diferentes Consulte la etiqueta interna de conectores para ver d nde colocar los cab...

Страница 7: ...es responsable por da os debidos a cableado incorrecto Neutro Neutro Neutro Panel de distribuci n A Panel de distribuci n B Neutro Tierra masa Tierra masa Diagrama de cableado B GRX TVI de 100 277 V...

Страница 8: ...a Cableado incorrecto La carga no est conectada al terminal SL1 SH1 Cableado incorrecto Veri que que la conexi n DL2 DH2 est cableada a una entrada del control de fase El indicador LED no se enciende...

Страница 9: ...A Renseignements Importants sur l Installation Installez conform ment tous les codes d lectricit locaux et nationaux V ri er pour les charges court circuit es durant les nouvelles installations avant...

Страница 10: ...de distribution distincts lesquels peuvent tre de phases ou de puissances diff rents Utiliser l tiquette des borniers internes pour voir ou atterrir les ls L tiquette montre deux bornes de raccordemen...

Страница 11: ...e contr le de signal 0 10 V NE PAS CONNECTER LA TENSION SECTEUR LutronR n est pas passible pour dommages dus un c blage erron Neutre Neutre Neutre Panneau de distribution A Panneau de distribution B N...

Страница 12: ...les lumi res C blage erron La charge n est pas connect e la borne de raccordement SL1 SH1 C blage erron V ri ez que la connexion DL2 DH2 soit vraiment c bl e l entr e de contr le de phase DEL n est pa...

Страница 13: ...o 10 A 16 A Motores 5 A 230 V CE 1 2 HP 100 120 V 11 2 HP 200 277 V P N 032443 Rev A Informa es importantes de instala o A instala o el trica deve ser feita de acordo com as normas locais e nacionais...

Страница 14: ...a etiqueta interna do bloco terminal para ver onde instalar os cabos A etiqueta mostra dois terminais de linha quente separados L1 H1 e L2 H2 L1 H1 a alimenta o de linha quente para alimentar a carga...

Страница 15: ...nal de controle de 0 10 V N O CONECTE VOLTAGEM DE LINHA A LutronR n o se responsabiliza por danos devidos conex o incorreta Neutro Neutro Neutro Painel de distribui o A Painel de distribui o B Neutro...

Страница 16: ...uma entrada de fechamento de contato de controle de fase A luz n o apaga Conex o incorreta A carga n o est conectada ao terminal SL1 SH1 Conex o incorreta Veri que se a conex o DL2 DH2 est realmente...

Страница 17: ...tionshinweise Die Anlage muss entsprechend allen nationalen und rtlichen Vorschriften f r elektrische Anlagen installiert werden berpr fen Sie die Lasten auf Kurzschl sse bevor Sie das GRX TVI verkabe...

Страница 18: ...st die unterschiedliche Phasen oder Spannungen enthalten k nnen Schlie en Sie die Leitungen der inneren Beschriftung der Klemmenbl cke entsprechend an Die Beschriftung zeigt zwei verschiedene Phasenkl...

Страница 19: ...alleitungen NICHT AN NETZSPANNUNG ANSCHLIESSEN LutronR haftet nicht f r Sch den durch fehlerhafte Verdrahtung Neutralleiter Neutralleiter Neutralleiter Verteilerkaster A Verteilerkaster B Neutralleite...

Страница 20: ...rungseingang verbunden ist Das Licht wird nicht ausgeschaltet Fehlerhafte Verkabelung Die Last ist nicht an die Klemme SL1 SH1 angeschlossen Fehlerhafte Verkabelung Stellen Sie sicher dass die Klemme...

Страница 21: ...ori driver 0 10 V Pilotaggio carico uorescente 0 10 V zona carico 1 Pilotaggio carico uorescente 0 10 V zona carico 1 Comando on off carico uorescente zona carico 2 Zona carico a incandescenza 3 Centr...

Страница 22: ...di distribuzione separati che possono essere su fasi diverse o avere tensioni di alimentazione diverse Per il collegamento corretto dei li fare riferimento alle etichette sulla morsettiera interna L e...

Страница 23: ...ra ATTENZIONE li per segnale di comando 0 10 V NON COLLEGARE ALLA TENSIONE DI RETE LutronR non responsabile per danni dovuti a cablaggi non corretti Neutro Neutro Neutro Quadro di distribuzione A Quad...

Страница 24: ...gio errato Assicurarsi che la linea DL2 DH2 sia effettivamente collegata a un ingresso a controllo di fase La lampada non si spegne Cablaggio errato Il carico non collegato al morsetto SL1 SH1 Cablagg...

Страница 25: ...ng m b t installatie Voer de installatie uit in overeenstemming met alle lokaal en nationaal geldende elektrotechnische voorschriften Controleer bij nieuwe installaties op kortgesloten belastingen voo...

Страница 26: ...fases of spanningen Bepaal waar de draden moeten komen aan de hand van de interne klembloksticker De sticker geeft twee aparte faseklemmen aan L1 H1 en L2 H2 L1 H1 is de fasevoeding die de verlichtin...

Страница 27: ...river Aarde Aarde OPMERKING 0 10 V stuursignaaldraden NIET AANSLUITEN OP NETSPANNING LutronR is niet aansprakelijk voor schade als gevolg van verkeerde bedrading Nul Nul Nul Verdeelbord A Verdeelbord...

Страница 28: ...ngesloten op een faseregeleenheid Led gaat niet branden Geen spanningsingang Controleer of er spanning op de interface staat Beperkte garantie Lutron zal een eenheid met een materiaal of fabrieksfout...

Страница 29: ...A 16 A 10 A 16 A 10 A 16 A 10 A 16 A 10 A 16 A 5 A 230 V CE 1 2 HP 100 120 V 11 2 HP 200 277 V 2 5 0 5 mm2 12 20 AWG NEMA 1 0 40 C 2 kg COOPERSBURG PA 18036 U S A 0 10V INTERFACE CONTROL Control Inpu...

Страница 30: ...02 mm 6 mm 298 mm 318 mm 102 mm 155 mm 84 mm N 2 DL 2 DH 2 L 1 H 1 100 277 V N 1 SL 1 SH 1 0 10 Volt L 2 H 2 100 277 V 1 2 A GRX TVI L1 H1 L2 H2 3 B GRX TVI L1 H1 L2 H2 L1 H1 L2 H2 GRX TVI 1 2 GRX TVI...

Страница 31: ...VI DL DH 0 10 V 0 10 V 0 10 V LutronR 20 A 10 A CE MCB 0 10 V L 2 H 2 100 277 V GRX TVI 0 10 V DL DH 0 10 V 0 10 V 0 10 V LutronR A B B 100 277 V GRX TVI 2 2 L2 H2 GRX TVI 100 277 V 1 L2 H2 GRX TVI 10...

Страница 32: ...lectronics Co Inc www lutron com product lutron com Lutron Electronics Co Inc 7200 Suter Road Coopersburg PA 18036 1299 1 800 523 9466 1 610 282 3800 1 610 282 1243 Lutron EA Ltd 6 Sovereign Close Lon...

Отзывы: