Installation and Operation Instructions  
Please Read Before Installing 
Occupant Copy

GRX-TVI Control Interface

Phase Control to 0-10 V

-

 

100-277 V

~  

50 / 60  Hz

Description 

The GRX-TVI provides 0-10 V

-

 control and ballast/driver switching 

capabilities in one enclosure. The GRX-TVI gives a 100-277 V

~

 

dimmer the ability to control current sourcing 0-10 V

-

 ballasts 

or LED drivers (loads) powered by 100-277 V

~

. The dimmer can 

be forward phase,reverse phase, or center phase

 

(for a sample of 

approved dimmers, see the list on spec sheet P/N 369247). The 
GRX-TVI provides switching relays that can handle the in-rush 
current for a circuit of ballasts/drivers. The GRX-TVI can also be 
used to switch any of the load types listed below.

Product Specifi cations 

Features

.............................. Provides a IEC PELV/NEC

R

 Class 2 

isolated 0-10 V

-

 output signal that 

conforms to EN60929 and IEC60929; 
Accepts any phase control signal;
Accepts a constant-gate drive 
fl uorescent signal (Control unit should 
be confi gured for fl uorescent load type) 

Input Power Rating

............100-277 V

~

  50/60 Hz 

H2/L2 Terminal

................... 20 mA  

Input Rating

  

DH2/DL2 Terminal

..............100 mA 

Input Rating

 

0-10 V

-

 Output Rating

..... 10 μA-300 mA - Sinks current only 

(maximum 150 ballasts/drivers)

 

Terminals 

Two 12 to 20 AWG (2.5 to 0.5 mm

2

) conductors 

 per 

terminal. 

Mounting 

NEMA Type 1 enclosure, indoor use only. 

Environmental  32 to 104 ˚F (0 to 40 ˚C). 
Weight 

4.25 lb (2 kg)  

COOPERSBURG, PA 18036 U.S.A.

0-10V INTERFACE CONTROL
Control Input:   

100-120V, 

220-240V 50/60Hz
Switches:
 100-277VAC

GRX-TVI

¨

Source/Load Type

230 V

~

 (CE)

100-277 V

~

 (Non-CE)

Fluorescent:
Electronic Capacitive 

Non-Dim

Other Manufacturer’s 0-10 V

-

Ballasts/drivers 

(0-10 V

-

 source only)

10 A

10 A

16 A

16 A

LED

10 A

16 A

Incandescent

10 A

16 A

Low-Voltage

10 A

16 A

Metal Halide

10 A

16 A

Neon/Cold Cathode

10 A

16 A

Motors

5 A @ 230 V

~

 CE

1/2 HP @ 100 - 120V

~

1

1

2

 HP @ 200 - 277 V

~

P/N 032443 Rev. A

  Important Installation Information 

•  Install in accordance with all national and local electrical codes. 

•  Check for short-circuited loads during new installations before wiring 

the GRX-TVI.   

WARNING - Shock Hazard.

 To avoid the risk of electric 

shock, locate and remove fuse or lock circuit breaker in the 
OFF position before proceeding. Wiring with the power ON 
could result in personal injury or death.

 

Note:

 Multiple power feeds could be provided. Ensure that all feeds 

are off before wiring.

•  Proper short circuit and overload protection must be provided at the 

distribution panel. You can use up to a 20 A (16 A for CE) maximum 
circuit breaker/MCB or equivalent (tripping curve C according to 
IEC 898/EN60898 is recommended) with adequate short circuit 
breaking capacity for your installation. 

•  Terminal blocks are rated for two 12 to 20 AWG (2.5 to 0.5 mm

2

wires per terminal.  

•  Strip 3/8 in (10 mm) of insulation from wires. 

 

 

 Note:

 277 V

~

 operation on the control terminal was a design feature 

added September 2013. To check whether your TVI has this feature, 
please ensure the front label of the TVI shows the acceptable voltage 
range as 100 - 277 V

~

 for the control input. Prior revisions of the unit 

had (2) L2/H2 terminals (one for 120 V

and one for 240 V

~

). The 

current design of the unit accepts a universal voltage (100 - 277

 

V

~

), 

so either of these terminals can be used for the control feed. They are 
internally tied together.

LUTRON

LUTRON

0-10 V

-

 Ballast/driver

0-10 V

-

 Ballast/driver

0-10 V

-

 Control Fluorescent Zone/Load 1

0-10 V

-

 Control Fluorescent Zone/Load 1

Switch Fluorescent Zone/Load 2

Incandescent Zone/Load 3

Control Unit / Dimmer

Power from 

Distribution 

Panel

GRX-

TVI

GRX-

TVI

Ballast/driver

Class 2/PELV Accessory Controls

3/8 in

(10 mm)

 

Note:

 When using a Control Unit, a GRX-TVI is required for each  0-10 V

-

 

fl uorescent zone. (A 3-zone Control Unit with two fl uorescent zones and 
one incandescent zone is shown as an example.)

System Wiring Layout Overview

Содержание Grafik Eye GRX-TVI

Страница 1: ...ode 10 A 16 A Motors 5 A 230 V CE 1 2 HP 100 120V 11 2 HP 200 277 V P N 032443 Rev A Important Installation Information Install in accordance with all national and local electrical codes Check for sho...

Страница 2: ...of the complete system is less than an MCB circuit breaker rating and L1 H1 and L2 H2 are both coming from the same phase one feed can be jumpered inside the enclosure as shown on Page 3 Wiring Diagr...

Страница 3: ...ONS Switched Line Hot Line Hot Line Hot Line Hot 0 10 V Ballast Driver 0 10 V Ballast Driver Earth Ground Earth Ground NOTICE 0 10 V Control Signal Wires DO NOT CONNECT TO LINE VOLTAGE LutronR is not...

Страница 4: ...connection is actually wired to a phase control input LED is not illuminated No Power Input Check that power is applied to the interface Limited Warranty Lutron will at its option repair or replace an...

Страница 5: ...r de acuerdo con todas las reglamentaciones de los c digos el ctricos nacionales y locales Veri que que no haya corto circuitos en las instalaciones nuevas antes de realizar el cableado del GRX TVI AD...

Страница 6: ...muestra una interfaz GRX TVI cableada desde dos paneles de distribuci n separados que pueden tener fases o voltajes diferentes Consulte la etiqueta interna de conectores para ver d nde colocar los cab...

Страница 7: ...es responsable por da os debidos a cableado incorrecto Neutro Neutro Neutro Panel de distribuci n A Panel de distribuci n B Neutro Tierra masa Tierra masa Diagrama de cableado B GRX TVI de 100 277 V...

Страница 8: ...a Cableado incorrecto La carga no est conectada al terminal SL1 SH1 Cableado incorrecto Veri que que la conexi n DL2 DH2 est cableada a una entrada del control de fase El indicador LED no se enciende...

Страница 9: ...A Renseignements Importants sur l Installation Installez conform ment tous les codes d lectricit locaux et nationaux V ri er pour les charges court circuit es durant les nouvelles installations avant...

Страница 10: ...de distribution distincts lesquels peuvent tre de phases ou de puissances diff rents Utiliser l tiquette des borniers internes pour voir ou atterrir les ls L tiquette montre deux bornes de raccordemen...

Страница 11: ...e contr le de signal 0 10 V NE PAS CONNECTER LA TENSION SECTEUR LutronR n est pas passible pour dommages dus un c blage erron Neutre Neutre Neutre Panneau de distribution A Panneau de distribution B N...

Страница 12: ...les lumi res C blage erron La charge n est pas connect e la borne de raccordement SL1 SH1 C blage erron V ri ez que la connexion DL2 DH2 soit vraiment c bl e l entr e de contr le de phase DEL n est pa...

Страница 13: ...o 10 A 16 A Motores 5 A 230 V CE 1 2 HP 100 120 V 11 2 HP 200 277 V P N 032443 Rev A Informa es importantes de instala o A instala o el trica deve ser feita de acordo com as normas locais e nacionais...

Страница 14: ...a etiqueta interna do bloco terminal para ver onde instalar os cabos A etiqueta mostra dois terminais de linha quente separados L1 H1 e L2 H2 L1 H1 a alimenta o de linha quente para alimentar a carga...

Страница 15: ...nal de controle de 0 10 V N O CONECTE VOLTAGEM DE LINHA A LutronR n o se responsabiliza por danos devidos conex o incorreta Neutro Neutro Neutro Painel de distribui o A Painel de distribui o B Neutro...

Страница 16: ...uma entrada de fechamento de contato de controle de fase A luz n o apaga Conex o incorreta A carga n o est conectada ao terminal SL1 SH1 Conex o incorreta Veri que se a conex o DL2 DH2 est realmente...

Страница 17: ...tionshinweise Die Anlage muss entsprechend allen nationalen und rtlichen Vorschriften f r elektrische Anlagen installiert werden berpr fen Sie die Lasten auf Kurzschl sse bevor Sie das GRX TVI verkabe...

Страница 18: ...st die unterschiedliche Phasen oder Spannungen enthalten k nnen Schlie en Sie die Leitungen der inneren Beschriftung der Klemmenbl cke entsprechend an Die Beschriftung zeigt zwei verschiedene Phasenkl...

Страница 19: ...alleitungen NICHT AN NETZSPANNUNG ANSCHLIESSEN LutronR haftet nicht f r Sch den durch fehlerhafte Verdrahtung Neutralleiter Neutralleiter Neutralleiter Verteilerkaster A Verteilerkaster B Neutralleite...

Страница 20: ...rungseingang verbunden ist Das Licht wird nicht ausgeschaltet Fehlerhafte Verkabelung Die Last ist nicht an die Klemme SL1 SH1 angeschlossen Fehlerhafte Verkabelung Stellen Sie sicher dass die Klemme...

Страница 21: ...ori driver 0 10 V Pilotaggio carico uorescente 0 10 V zona carico 1 Pilotaggio carico uorescente 0 10 V zona carico 1 Comando on off carico uorescente zona carico 2 Zona carico a incandescenza 3 Centr...

Страница 22: ...di distribuzione separati che possono essere su fasi diverse o avere tensioni di alimentazione diverse Per il collegamento corretto dei li fare riferimento alle etichette sulla morsettiera interna L e...

Страница 23: ...ra ATTENZIONE li per segnale di comando 0 10 V NON COLLEGARE ALLA TENSIONE DI RETE LutronR non responsabile per danni dovuti a cablaggi non corretti Neutro Neutro Neutro Quadro di distribuzione A Quad...

Страница 24: ...gio errato Assicurarsi che la linea DL2 DH2 sia effettivamente collegata a un ingresso a controllo di fase La lampada non si spegne Cablaggio errato Il carico non collegato al morsetto SL1 SH1 Cablagg...

Страница 25: ...ng m b t installatie Voer de installatie uit in overeenstemming met alle lokaal en nationaal geldende elektrotechnische voorschriften Controleer bij nieuwe installaties op kortgesloten belastingen voo...

Страница 26: ...fases of spanningen Bepaal waar de draden moeten komen aan de hand van de interne klembloksticker De sticker geeft twee aparte faseklemmen aan L1 H1 en L2 H2 L1 H1 is de fasevoeding die de verlichtin...

Страница 27: ...river Aarde Aarde OPMERKING 0 10 V stuursignaaldraden NIET AANSLUITEN OP NETSPANNING LutronR is niet aansprakelijk voor schade als gevolg van verkeerde bedrading Nul Nul Nul Verdeelbord A Verdeelbord...

Страница 28: ...ngesloten op een faseregeleenheid Led gaat niet branden Geen spanningsingang Controleer of er spanning op de interface staat Beperkte garantie Lutron zal een eenheid met een materiaal of fabrieksfout...

Страница 29: ...A 16 A 10 A 16 A 10 A 16 A 10 A 16 A 10 A 16 A 5 A 230 V CE 1 2 HP 100 120 V 11 2 HP 200 277 V 2 5 0 5 mm2 12 20 AWG NEMA 1 0 40 C 2 kg COOPERSBURG PA 18036 U S A 0 10V INTERFACE CONTROL Control Inpu...

Страница 30: ...02 mm 6 mm 298 mm 318 mm 102 mm 155 mm 84 mm N 2 DL 2 DH 2 L 1 H 1 100 277 V N 1 SL 1 SH 1 0 10 Volt L 2 H 2 100 277 V 1 2 A GRX TVI L1 H1 L2 H2 3 B GRX TVI L1 H1 L2 H2 L1 H1 L2 H2 GRX TVI 1 2 GRX TVI...

Страница 31: ...VI DL DH 0 10 V 0 10 V 0 10 V LutronR 20 A 10 A CE MCB 0 10 V L 2 H 2 100 277 V GRX TVI 0 10 V DL DH 0 10 V 0 10 V 0 10 V LutronR A B B 100 277 V GRX TVI 2 2 L2 H2 GRX TVI 100 277 V 1 L2 H2 GRX TVI 10...

Страница 32: ...lectronics Co Inc www lutron com product lutron com Lutron Electronics Co Inc 7200 Suter Road Coopersburg PA 18036 1299 1 800 523 9466 1 610 282 3800 1 610 282 1243 Lutron EA Ltd 6 Sovereign Close Lon...

Отзывы: