9
www.luminite.co.uk
No Sound Frequencies & Patterns
Code Description
1 800 Hz to 950 Hz swept at 120 Hz
DDDDD
Banshee Buzz LF
2 800 Hz to 950 Hz swept at 9 Hz
UDDDD
Banshee Fast Sweep LF
3 800 Hz to 950 Hz swept at 3 Hz
DUDDD
Banshee Slow Sweep LF
4 Continuous at 900 Hz
UUDDD
Banshee Continuous LF
5 830 Hz to 970 Hz swept at 9 Hz
DDUDD
Banshee Fast Sweep LF (New)
6 830 Hz to 970 Hz swept at 1 Hz
UDUDD
Medium Sweep LF
7 Continuous at 950 Hz
DUUDD
Continous LF
8 Intermittent at 950 Hz 1 sec on, sec off
UUUDD
Back Up Alarm LF
9 Alternating 800Hz/100 Hz at 1 Hz
DDDUD
Alternate LF
10 800 Hz to 100 Hz swept at 0.5 sec
UDDUD
Medium Sweep LF
11 Alternating Tones 800Hz/950 Hz at 3 Hz
DUDUD
Alternate LF
12 2400 Hz to 2900 Hz at 120 Hz
UUDUD
Banshee Buzz HF
13 2400 Hz to 2900 Hz at 9 Hz
DDUUD
Banshee fast Sweep HF
14 2400Hz to 2900 Hz at 3 Hz
UDUUD
Banshee Slow Sweep HF
15 Continuous 2900 Hz
DUUUD
Banshee Continuous HF
16 2450 Hz to 3100 Hz swept at 9 Hz
UUUUD
Banshee Fast Sweep HF (New)
17 Intermittent at 2900 Hz 1 sec on, 1 sec off
DDDDU
Back Up Alarm HF
18 Alternating Tones 2400Hz/2900 Hz at 3 Hz
UDDDU
Alternate HF
19 500 Hz rising to 1200 Hz over 3.5 sec, silence 0.5 sec
DUDDU
Slow Whoop
20 1200 Hz falling to 500 Hz over 1 sec, silence 10mS
UUDDU
Din Tone (DK)
21 554 Hz for 100 mS and 440 Hz over 1 sec, silence 10mS
DDUDU
French Fire Sounder
22 420 Hz reapeting 0.625 sec on, 0.625 sec off
UDUDU
Australian Alert Signal
23 500 Hz to 1200 Hz sweeping 3.75 secs on, 0.25 secs off
DUUDU
Australian Evacuation Signal
24 950 Hz for 0.5 sec on, 0.5 sec off for 3 phases, silence for 1.5 secs
UUUDU
US Temporal Tone LF
25 2900 Hz for 0.5 sec on, 0.5 sec off for 3 phases, silence for 1.5 secs
DDDUU
US Temporal Tone HF
26 Intermittent 660 Hz 150 mS on, 150 mS off
UDDUU
Swedish Tone (Fire)
27 Continuous 660 Hz
DUDUU
Swedish Tone (All Clear)
28 Intermittent 970 Hz 500 mS on, 500mS off
UUDUU
ISO8201 LF
29 Intermittent 2900 Hz 500 mS on, 500mS off
DDUUU
ISO8201 HF
30 Yodel 800 Hz /100 Hz, 0.25 sec
UDUUU
BT Banshee (FP1063.1)
31 Continuous 100 Hz
DUUUU
BT Banshee (FP1063.1)
32 Bell Tone
UUUUU
Bell Tone
D = Down
U = Up
* U = Up, D = Down
**Sound table for Vimpex Sounders
Initiate a Silent Test
*Only Master units can initiate Silent Tests across the Alertex system
**Please note that Annunciator units cannot initiate a silent test
Содержание Alertex NXECSB