10
www.luminite.co.uk
To initiate a silent test:
1. Insert the silver master key into a ALERTEX master unit
2. Turn the key clockwise for 10 seconds until the LED lights and then
return it anticlockwise to the neutral position
3. Wait until the LED on the callpoint starts to flash once a second. The
system is now in silent test mode
4. Activate a call point. This can be the one on the master unit or any
other callpoint on the system
5. All the beacons on the system will now flash
6. Reset the call point that was activated by using the plastic cross key
7. After a while the beacons will turn off. Wait until all beacons are off
8. Wait until the LED on the master unit or other callpoints returns to
flashing once a second. This will take a minite or so
9. When the LED returns to flashing once a second another callpoint can
be tested
10. To test another call point go back to number 6
11. To take the system out of silent test mode turn master unit key
clockwise for 3 seconds and return to the neutal position
12. Waitfor the LED on the master unit to go out. The sytem is now
operating normally
How to Stop and Reset the Alarm
After the system has been activated, you need to use a Alertex Master
unit to reset it:
1. Insert the silver master key provided into a Alertex master unit
2. Turn the key clockwise for 3 seconds and then return it to the neutral
position
3. All units on the same site will begin to reset
4. Depending on the size of the site, the system may require an additional
reset. In this case, wait 3 minutes and then reset the system from the
master unit again