same site number. Although it cannot be set with a unit number, it counts
as one of the 64 units and reduces the total available units to 63.
Call Repeat
Master Unit
Call Period
Time Set
Enables or disables which units can act as a repeater to relay the wireless
transmission across longer distances.
Call repeating is disabled by default
and should only be enabled on units that are required to create a larger
mesh network as battery life is affected.
Alertex sounder or annunciator
/ beacon units have a wireless transmission range of up to 1km. Units set
to call repeat can relay the transmission up to 16 times out of the initial
1km radius, providing a maximum line of sight transmission range of up
to 16km.
Enables or disables which units are identified as Master units. Master
units are the only units that are able to reset the system post-activation
and are fitted with a master reset key.
Determines how frequently the units will check in with the IP Masthead
to give their status and provide updates such as low battery or poor signal
notifications. The frequency of the call period can be set from 3 to 99
minutes and is
set to 99 minutes by default.
From 3 to 50 minutes, the
value can be increased and decreased in 1 minute increments (ie. 4, 5, 6,
7, etc...). From 50 to 99 minutes, the value can be increased and decreased
in 5 minute increments (ie. 55, 60, 65, etc...).
More frequent call periods
can affect the battery life of Alertex units.
Determines how long the sounder or annunciator / beacon will produce
an audible alert.
By default, it is set to 10 minutes.
This means that after
the initial 10 minute period is over, the units will stop creating an audible
alert but will continue to produce a visible alert. The beacon can be set
to produce an audible alert from 1-30 minutes. Setting the TS to 0 will
cause the beacon to produce an audible alert indefinitely until the system
is reset.