4.2.4 Top Thread Installation-Hoisting Installation
① Fix the thread on the top of the probe with a nut
② Use a protective tube for the probe inlet
Flange mounting, installed in very short nozzles
The most ideal installation is to directly install the instrument on a flat-topped container, without using
a pipe, the circular opening on the container can be sufficient to fix the flange or universal joint for
installation. The probe emission surface is below the reference surface.
▲
The installation on the tank, pool, cover and bracket is basically the same as above.
★ After the probe is installed, the emission surface of the probe must expose the cover plate or the
waveguide. Do not shrink inside the cover or waveguide.
4.2.5 Measuring liquid
4.2.5.1 Flat-top tank
Flat-top tanks generally have a very short tube. The reference surface of the tube is the bottom
surface of the flange. The length of the tube is
≤
60mm, the diameter of the tube is
≥
100mm, and the
inner wall of the tube is flat without burrs or protrusions. The emission surface can be measured 3cm
below the bottom surface of the flange.