Lucent Technologies Lineage
®
2000 125A Ferroresonant Rectifier J85502C-1
6 - 12 Testing
Issue 8 July 1999
5. Restart the rectifier using the RS switch on the test set.
6. Adjust the voltage to approximately 26.0 volts (24-volt
rectifier) or 52.0 volts (48-volt rectifier). The RFA lamps
on the rectifier and the test set should go out.
Control (TR) Test
1. Press and hold the transfer rectifier (TR) switch on the test
set for 5 seconds. The rectifier should turn off simulating a
remote shutdown from the controller. The POWER ON
light should go off. The digital meter on the rectifier
should go off, and the TRH lamp on the test set should
light.
2. Release the switch. The rectifier should restart and the
TRH lamp should go out.
3. Press the HV switch on the test set. The rectifier should
continue to operate.
Selective High
Voltage
Shutdown
(SHVSD) and
Restart
1. Adjust the test load so that the rectifier delivers 12-19A, 10
to 15 percent of its rated amperage.
2. Momentarily press the HV switch on the test set. The
rectifier should shut down and the RFA lamps on the
rectifier and the test set should light.
3. Momentarily press the RS switch on the test set. The
rectifier should restart and both RFA lamps should go off.
Note
To increase the upper range of the voltage adjustment, do one
or both of the following:
•
Temporarily open the R– lead on the test box. (The lead
goes to P2A-2 on CM2.)
•
Short resistor R22 (24-volt version) or R21 (48-volt
version) on the CM1 board.
When this step is completed restore the original conditions to
straps Q and T and restore R21 or R22.