Lucent Technologies Lineage
®
2000 125A Ferroresonant Rectifier J85502C-1
5 - 4 Installation
Issue 8 July 1999
on ladder racks. Experience has shown that the use of flexible
cables (welding type cables) makes installation of this type
wiring much simpler. The terminals are sized to fit KS-24194 L2
wire, which is very flexible.
Figure 5-1 shows the dc output conduit hole. Figure 5-4 shows
the dc output wire termination points for both negative and
positive polarity. Table 5-B specifies the dc output cable size,
T&B connectors and crimp die. Also see note 57 on J-drawing,
J85502C-1.
Table 5-B: DC Output Requirements
Amps
Output
Wire Size*
Output Conduit
Trade Size
(inches)
Connectors
Required
T&B
Crimp Die
125
1/0 AWG
1-1/2
1 stud with
anti-rotation tab,
Ground: 5/16" dia.,
T&B 54158
Battery: 3/8" dia.,
T&B 54110
Black
*Use KS-24194 L2 wire. It is a flexible, stranded copper wire, rated 600 volts;
stranding meets American Society for Testing and Materials (ASTM) B 172
Class I. This non-halogen, insulated wire is rated 90°C. The insulation has a
combustibility rating of 28% minimum as determined by ASTM D2863. Wire
sizes were chosen to limit the voltage drop to 2 volts where the cable loop is
approximately 200 feet.