Lucent Lineage
®
2000 ECS Battery Plant H569-408
Issue 2 July 1996
Product Description 2 - 1
2
Product Description
Plant
Specifications
Table 2-A. LINEAGE® 2000 Battery Plant Specifications -Model H569-408
Input Voltage
180-264 Vac (208/220/240 Vac nominal)
Input Frequency
47-63 Hz (50/60 Hz nominal)
Operating Voltage
40-60.0 Vdc (48 Vdc nominal)
Float Voltage
47-58.5 Vdc (48 Vdc nominal)
Plant Current Rating
300 amperes
Plant Shunt
300 amperes maximum at 50 millivolts
LVD/R Voltage Settings
40.5 or 42.5 Vdc
Controller
Basic: 113A;
Microprocessor option circuit pack: BAB1;
Datalogger option circuit pack: BAC1, BAC2
Rectifier Shelf Assembly
2 maximum, each mounts 3 rectifiers
Rectifiers
Type: LINEAGE® 2000 SR50/-48V
Rating: -48 Vdc nominal, 50 amperes
Number: 6 maximum
Batteries
Type: LINEAGE® 2000 2VR375E
Rating: 375 Ah per string
Number: 7 strings maximum