6
Battery Connection Panels
Overview
Function
Batteries are connected to the GPS 4804AP cabinets on battery
connection panels located in the cabinet directly below the ac input
panel.
All panels include the battery shunts that communicate with the
controller to provide battery current information. The panels may
include low voltage battery disconnect/reconnect (LVBD/R) contactors
or low voltage load disconnect/reconnect contactors (LVLD/R). An
Alarm card provides local/manual control of the contactors.
Notes: 1) The Alarm card is common for the Battery Connection
Panels and the DC Distribution Panels.
2) When LVLD/R Contactor is selected, six positions in the DC
Distribution will be assigned as critical loads.
Cross Reference of
Cabinets and
Battery Connection
Panels
Table 6-A identifies which cabinet uses each of the battery connection
panels.
Illustrations
The battery connection panels are shown in Figures 6-1 through 6-4.
Table 6-A: Battery Connection Panels
Panel
Description
Figure
H 569-450 G30
Battery Connection Panel with 2 x 400A Battery Contactors
(LVBD/R)
Figure 6-1
H 569-450 G31
Battery Connection Panel with 2 x 400A Battery Contactors
(LVBD/R), 1 x 400A contactor for DC Distribution (LVLD/R)
Figure 6-2
H 569-450 G32 Battery Connection Panel 1 x 600A battery Contactor (LVBD/R) Figure 6-3
H 569-450 G33
Battery Connection Panel with 1 x 600A battery Contactor
(LVBD/R), 1 x 400A contactor for DC Distribution (LVLD/R)
Figure 6-4