Lucent Technologies Galaxy Power System 4804AP H569-450
Issue 1 June 2000
Installation 11 - 49
Power Up and Installation Completion, continued
Voltage Calibration
Voltage Calibration
Step
Action
1
Using a calibrated digital voltmeter (DVM), measure the
system voltage from the front panel voltage test jacks.
2
If the voltage on the controller display does not match the DVM
reading, adjust the controller display. To move to the correct
screen to make the adjustment, follow the appropriate
procedure below:
•
Galaxy Millennium controllers, press the following key
sequence:
Main
→
Config
→
Plant
→
Enter
Move to ADJ PLV on the menu.
•
Galaxy Vector controllers, use the following key sequence:
Config
→
Up arrow key (until FPC is on the display)
→
Enter
3
Use the ADJUST keys to calibrate the system voltage to match
the reading of the DVM. Press ENTER to use the new
calibrated system voltage. Press the ESCAPE key until the
default screen is displayed. Verify that the system voltage
reading reflects the new value.