Lucent Technologies Lineage
®
2000 Battery Management System ED-83241-30
Issue 5 March 1997
Setup 4 - 1
4
Setup
DIP Switch
Settings
The Lucent Technologies Battery Management System may be
customized to meet different applications by selecting the
appropriate settings and functions on the DIP switches provided
on CP5. The DIP switches used for this purpose are SW100,
SW101 and SW102. The location of the switches is shown in
Figure 3-17. Tables that show the DIP switch settings are
provided on the CP5 cover. The function of each switch is
defined below.
SW100
Positions 1 and 2 select the T1 setpoint. The values range from
20°C to 35°C in 5°C increments.
Positions 3 and 4 select the T2 and MJT setpoint. The values
range from 40°C to 55°C in 5°C increments.
SW101
Positions 1 and 2 select the (MNT) Minor Temperature Alarm
setpoint. The values range from 30°C to 45°C in 5°C increments.
Position 3 provides compatibility with either a 23 cell or 24 cell
battery plant.
Position 4 allows the user to select temperature units in degrees
Fahrenheit or Celsius for the LCD display.
SW10
Positions 1, 2 and 3 select the current limit setpoint for the
recharge current control feature. The current limit ranges from
12.5 Amps to 100 Amps in 12.5 Amp increments.