Lucent Technologies Lineage
®
2000 Battery Management System ED-83241-30
5 - 4 Operations
Issue 5 March 1997
To display the highest battery temperature in Celsius the channel
must be configured as follows:
Channel Description Highest Battery Temp
Input Type
+DC
Range
6V
Scale Factor
55.556
Transducer Offset
0.32
Alarm Threshold
An upper or lower user defined
threshold may be set to warn the user if
the maximum battery temperature is
greater/less than expected. This
threshold could be set to a different
temperature than the Minor
Temperature Alarm. Also, this
threshold could be set to the same
temperature as T1 to let the user know
when the Battery Management System
is actively controlling the plant voltage.
The number entered is in degrees
Celsius.
Units
Degrees Celsius