Lucent Technologies Lineage
®
2000 Battery Management System ED-83241-30
2 - 2 Product Description
Issue 5 March 1997
Feature
Summary
•
Compatible with the Lineage
®
2000 ECS Controller
Datalogger Board (CP3) and Microprocessor Board (CP2).
•
User selectable temperature compensation algorithm
customizes the system for each battery plant.
•
The system monitors and controls up to two battery strings.
•
Flexible design allows the system and its features to grow as
the battery plant and needs grow.
•
Battery Management System is available in a retrofit kit for
upgrading existing J85500D battery plants.
Temperature Compensation
Range
68° - 131°F (20° - 55°C)
Temperature Measurement
Accuracy
+/-3.6°F (2°C) from 68° - 131°F (20° - 55°C)
+/-5.4°F (3°C) from 32° - 158°F (0° - 70°C)
Voltage Sensors
One set per battery string that measures the
voltage in two groups
Voltage Measurement
Accuracy
+/-0.5%
Current Sensors
One per battery string.
Hall-effect device with a gain of 33.3 mV/A
Recharge Current Compensation
Settings
12.5A - 100A in 12.5A increments
Current Measurement
Accuracy
+/-1.0% full scale accuracy
+/-0.6A zero offset accuracy
Analog Outputs:
Ambient Temperature
10 mV/°F
Highest Battery
Temperature
10 mV/°F
Battery String 1 Current
33 mV/A
Battery String 2 Current
33 mV/A
Battery Management Fail
Alarm (BMF)
Closure to RG
Minor Voltage Alarm
(MNV)
Closure to RG
Minor Temperature Alarm
(MNT)
Closure to RG
Major Temperature Alarm
(MJT)
Closure to RG
Table 2-A: Battery Management System (CP5) Specifications