LubriMist
®
Model JD
Oil Mist Generating System
Installation and Operating Manual
Page 90 of 152
Input Register Addresses
Address (HEX) Message frame Address Description
01
=
00
---
Air Pre-heater Enable Temp.
02
=
01
---
Bulk Oil Reservoir Level
03
=
02
---
Ambient Temp.
04
=
03
---
High Air Temp.
05
=
04
---
Air Temp.
06
=
05
---
Mist Density
07
=
06
---
Mist Press.
08
=
07
---
Regulated Air Press.
09
=
08
---
Supply Air Press.
a
=
09
---
Supply Oil Press.
b
=
0a
---
High Air Pre-heater Temp.
c
=
0b
---
Bulk Oil Reservoir Temp.
d
=
0c
---
Air Pre-heater Temp.
Message frame being received
Input Register, Function code 04, this data will come from the JD
([01] [04] [02] [00] [44] [b9] [03]).
1) Device I.D. in
Modscan screen has to
be the same as the JD
location
2) In the Modscan
screen Modbus point
type & Function code are
the same thing
3) Data Received,
consisting of length and
the status being polled
4) Cyclical Redundancy
Checking or CRC
[01]
[04]
([02]) ([00][44])
[b9] [03]
The first two sets of numbers are the same as the previous.
1) The device ID 01.
2) The Function code 04.
3) Data Received---Has 3 sets of numbers a [02] and a [00] [44]. The first set of numbers [02] represent the
number of bites of the value status being received (black field), meaning the length in the Modscan screen is
1 so a [02] is received in the message frame (black field). If the length in the Modscan screen were 2 the
data received would be [04], if it were 3 then it would be [06] and so on.
The second set of numbers is the value being polled in HEX, Example [00] [44] = 68 in decimal, this is value
that’s received for the Bulk Oil Reservoir Level. (This would be in gallons)
If the length were 2 in the Modscan screen and the starting HEX Address were 02, then from the previous
statement. The data received would be [00] [44] [00] [46]. The first two bites of data [00] [44] bulk Oil
Reservoir Level would have a decimal value of 68 in gallons and the second set of data bites [00] [46] would
be the Ambient Temp. with a decimal value of 70 (this would be degrees in Fahrenheit).
4) Cyclical Redundancy Check--- CRC, is a number assigned by the computer and cannot be changed by
the user.
Содержание JD
Страница 2: ...LubriMist Model JD Oil Mist Generating System Installation and Operating Manual Page 2 of 152 ...
Страница 35: ...LubriMist Model JD Oil Mist Generating System Installation and Operating Manual Page 35 of 152 COMMISSIONING ...
Страница 43: ...LubriMist Model JD Oil Mist Generating System Installation and Operating Manual Page 43 of 152 OPERATING GUIDE ...
Страница 110: ...LubriMist Model JD Oil Mist Generating System Installation and Operating Manual Page 110 of 152 TROUBLE SHOOTING GUIDE ...