Active chilled beams HDF-600, ceiling installation
4.2.
Performance data
Size 1200, 2-way diffusion, 2-pipe system
V
P
cfm
Δ
p
in H
2
O
L
A18
dB(A)
L
wA
dB(A)
Q
P
/
Δ
t
BTU/h
·
Δ
t
-1
Q
c
/
Δ
t
BTU/h
·
Δ
t
-1
Q
c
1)
BTU/h
W
oc /
Δ
p
w
gpm / Ft H
2
O
37
0.28
15
21
40
95
2439
0.75 / 1
45
0.40
20
26
48
114
2903
54
0.60
25
31
57
124
3255
47
0.28
19
25
49
103
2750
56
0.40
24
30
61
116
3162
67
0.60
29
35
72
131
3645
58
0.28
23
29
63
106
3023
70
0.40
27
33
76
122
3526
84
0.60
33
39
91
141
4134
73
0.28
26
33
78
110
3366
89
0.40
31
37
95
125
3930
106
0.60
36
42
114
150
4702
Size 1800, 2-way diffusion, 2-pipe system
V
P
cfm
Δ
p
in H
2
O
L
A18
dB(A)
L
wA
dB(A)
Q
P
/
Δ
t
BTU/h
·
Δ
t
-1
Q
c
/
Δ
t
BTU/h
·
Δ
t
-1
Q
c
1)
BTU/h
W
oc /
Δ
p
w
gpm / Ft H
2
O
59
0.28
17
23
63
152
3856
0.75 / 1.5
72
0.40
19
25
76
179
4563
86
0.60
24
30
91
194
5110
74
0.28
18
24
80
165
4372
90
0.40
23
29
95
182
4991
108
0.60
28
34
114
209
5787
93
0.28
22
28
99
167
4770
112
0.40
27
33
120
192
5559
135
0.60
32
38
144
222
6531
116
0.28
26
32
124
175
5345
141
0.40
30
36
150
198
6229
168
0.60
35
41
179
236
7439
Содержание HDF-600