Chapter 6 High-speed Link
6-3
6.3 Operation Sequence through High-speed Link
<Select high speed link >. High speedlink window: open the high speed link setting
window of XG-PD
<Seelct high speed link parameters >.
High speed link 1~12: set up according to the No.of the communication
modules in use (select high speedlink 1 whenusing 1 communication module
* For XGB, only High speed link 1~2 are supported
<High speed link setting (link setting)>.
1. Module type: RAPIEnet
2. Slot No.: XGK/I: 0 ~ 11, XGB: 1~10
3. Transmission/reception period: 5ms ~ 1s
< High speed link setting (register list)>.
1. Mode: transmission or reception (transmission cannot be set up, Designate
correspondent station No. for reception)
2. Station No.: 0 ~ 63
3. Block No.
XGK/I: 0 ~ 127 (TX count 64, RX count 128) blocks are available
XGB: 0 ~ 64 (TX count 64, RX count 64) blocks are available
TRX data is classified by station number and block number
4. Read area, Save area
5. Size (1 ~ 200 word)
<Online (after locak access)>.
1. Write: download high speed link parameters from XG-PD to CPU.
<Link allowability setting >.
1. Seelct one of high speed link 1 ~ 12 (For XGB, 1~2)
Enable the High speed link at the XG-PD.
<Destination station setting >.
Set up the destination station in the same manner as hereinabove.