Chapter 1 Introduction
1-3
1.3 Product Configuration
1.3.1 Type
It describes product spec. of XGT RAPIEnet I/F module.
Type
Description
Remarks
XGK/I/R
XGL-EIMT
Electric 2 ports
Category 5 or above
XGL-EIMF
Optical 2 ports
XGL-EIMH
Electric 1 port, optical 1port
XGB
XBL-EIMT
Electric 2 ports
Option
XOL-EIMT
Electric 2 ports
Multi-mode optical cable of two wires
XOL-EIMF
Optical 2 ports
1.3.2 Number of modules available by CPU types
RAPIEnet I/F Modules can be installed up to 24 sets regardless of main or extension bases. It is recommended to
install the modules on the main base for maximum usability. The table below shows the types of services available
for each CPU. You can use this table for system construction considering the number of communication modules.
Classification
XGK
XGI
XGR
note1)
XGB
PC I/F
Card
CPUH
CPUH
CPUA
CPUS
CPUE
CPUU
CPUH
CPUS
CPUE
CPUH/F
CPUH/T
XBC
Max. number of
modules using high
speed link
12
note2)
2
1
Max. number of
modules using P2P
8
note2)
2
-
Max. number of
module (including
the modules using
exclusive services)
24
note2)
2
1
Note 1) The RAPIEnet I/F Module can be installed on the main base only when using XGR CPU.
Note
Note1) Installation position of RAPIEnet I/F module according to CPU type
- When using XGK/XGI CPU, you can install the RAPIEnet I/F module at main both base and expansion base.
- When using XGR CPU, you can install the RPIEnet I/F module at main base only.
Note2) The number of
XGR’s module using P2P
- For RAPIEnet, it can be installed at main base so the number of module using High speed link and P2P is up to 6.