Chapter 10 Diagnostic Function
10-11
10.5.2 Diagnosis of Communication Module through XG5000
XG5000 program can be used to monitor the communication Module simply to check for any error thereon. Connect RS-
232C connector with CPU port and then select [Online]
[PLC History] -> [PLC Errors/Warnings] in XG5000.
[Fig. 10.5.2] PLC history detail information monitor
If a hardware error or a CPU interface error occurs on the Module, LED of the communication Module itself operates
abnormally in general, whose status can be monitored simply through its dedicated program.
[Fig. 10.6.2] shows error/warning information through PLC History on the XG5000 [Online] menu, which can be resolved
by referring to “Details/Remedy”.
10.5.3 Checking module healthiness with system log
Healthiness of communication modules can be roughly checked with XG-PD software. Connect CPU module via RS-
232C or USB connector. In the System Diagnosis window of the XG-PD, right-click the RAPIEnet I/F Module, and select
System Log to open the log window.
(1) Memory area log
Error occurrence and service provision can be checked.
[Fig. 10.6.3] shows the memory area log of the System Log.