7. Function List
7-16
7.4 I/O Group
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
I 0
[Jump code]
0/63
This parameter sets the code
number to jump
1
O
I 1
[Filter time
constant for
V0 input]
0/9999
This is used to adjust the
analog voltage input signal via
keypad potentiometer.
10
O
I 2
[V0 input Min
voltage]
0/10
[V]
Set the minimum voltage of
the V0 input.
0
O
I 3
[Frequency
corresponding
to I 2 ]
0/400
[Hz]
Set the inverter output
minimum frequency at minimum
voltage of the V0 input.
0.0
O
I 4
[V0 input Max
voltage]
0/10
[V]
Set the maximum voltage of
the V0 input.
10
O
I 5
[Frequency
corresponding
to I 4]
0/400
[Hz]
Set the inverter output
maximum frequency at maximum
voltage of the V0 input.
60.0
O
I 6
[Filter time
constant for
V1 input]
0/9999
Set the input section’s internal
filter constant for V1 input.
10
O
I 7
[V1 input Min
voltage]
0/10
[V]
Set the minimum voltage of
the V1 input.
0
O
I 8
[Frequency
corresponding
to I 7]
0/400
[Hz]
Set the inverter output
minimum frequency at minimum
voltage of the V1 input.
0.0
O
I 9
[V1 input max
voltage]
0/10
[V]
Set the maximum voltage of
the V1 input.
10
O
I10
[Frequency
corresponding
to I 9]
0/400
[Hz]
Set the inverter output
maximum frequency at maximum
voltage of the V1 input.
60.0
O
I11
[Filter time
constant for I
input]
0/9999
Set the input section’s internal
filter constant for I input.
10
O
I12
[I input
minimum
current]
0/20
[mA]
Set the Minimum Current of I
input.
4
O
Содержание SV004iC5-1F