3. Wiring
3-3
WARNING
Use the Type 3 grounding method (Ground impedance: Below
100ohm).
Use the dedicated ground terminal to ground the inverter. Do not use
the screw in the case or chassis, etc for grounding.
☞
Note : Remove front and bottom cover before starting grounding.
☞
Caution : Follow the specifications below when grounding the inverter.
Model
004iC5, 008iC5 – 1,1F
015iC5, 022iC5 – 1,1F
Wire size
2mm
2
2mm
2
Lug
2mm
2
, 3φ
2mm
2
, 3φ
Ground
impedance
Below 100 ohm
Below 100 ohm
Dedicated Ground
Terminal
Dedicated
Ground Terminal