7. Function List
7-3
7.2 Function Group 1
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
F 0
[Jump
code]
0/60
This parameter sets the
parameter code number to
jump.
1
O
F 1
[Forward/
Reverse
run disable]
0/2
0 Fwd and rev run enable
0
X
1 Forward run disable
2 Reverse run disable
F 2
[Accel
pattern]
0/1
0
Linear
0
X
F 3
[Decel
pattern]
1
S-curve
F 4
[Stop mode
select]
0/2
0 Decelerate to stop
0
X
1 Stop via DC brake
2 Free run to stop
F 8
1)
[DC Brake
start
frequency]
0/60
[Hz]
This parameter sets DC
brake start frequency.
It cannot be set below F23 -
[Start frequency].
5.0
X
F 9
[DC Brake
wait time]
0/60
[sec]
When DC brake frequency
is reached, the inverter holds
the output for the setting time
before starting DC brake.
0.1
X
F10
[DC Brake
voltage]
0/200
[%]
This parameter sets the
amount of DC voltage applied
to a motor.
It is set in percent of H33 –
[Motor rated current].
50
X
F11
[DC Brake
time]
0/60
[sec]
This parameter sets the time
taken to apply DC current to a
motor while motor is at a stop.
1.0
X
F12
[DC Brake
start
voltage]
0/200
[%]
This parameter sets the
amount of DC voltage before a
motor starts to run.
It is set in percent of H33 –
[Motor rated current].
50
X
F13
[DC Brake
start time]
0/60
[sec]
DC voltage is applied to the
motor for DC Brake start time
before motor accelerates.
0
X
F14
[Time for
magnetizing
a motor]
0/60
[sec]
This parameter applies the
current to a motor for the set
time before motor accelerates
during Sensorless vector
control.
1.0
X
1) : Set F4 to 1 (Stop via DC brake ) to view this function
Содержание SV004iC5-1F
Страница 8: ......
Страница 22: ...3 Wiring 3 6 ...
Страница 38: ...5 Programming Keypad 5 14 ...
Страница 42: ...6 Basic Operation 6 4 ...
Страница 64: ...7 Function List 7 22 ...
Страница 74: ...9 Specifications 9 4 ...