Table of Functions
200
8.16
User/Macro mode
–
Traverse Operation Function
Group (
MC2)
Traverse Operation Function Group (U&M
MC2)
No. LCD Display
Name
Setting Range
Initial Value
00
Jump Code
Jump code
0
–
99
1
01
Acc Time
Acceleration time
0
–
600 (sec)
Below 75 kW
20
Above 90 kW
60
02
Dec Time
Deceleration time
0
–
600 (sec)
Below 75 kW
30
Above 90 kW
90
03
Cmd Source
Command source
0
–
5
1:Fx/Rx-1
04
Freq Ref Src
Frequency reference source
0
–
9
0:Keypad-1
05
Control Mode
Control mode
0
–
5
0:V/F
06
App Mode
Applied function selection
0
–
4
1:Traverse
07
Trv Apmlit %
Traverse operating range
0
–
20 (%)
0.0
08
Trv Scramb %
Traverse scramble magnitude
0
–
50 (%)
0.0
09
Trv Acc Time
Traverse acceleration time
0.1
–
600 (sec)
2.0
10
Trv Dec Time
Traverse deceleration time
0.1
–
600 (sec)
2.0
11
Trv Offset Hi
Traverse offset upper limit
0
–
20 (%)
0.0
12
Trv Offset lo
Traverse offset lower limit
0
–
20 (%)
0.0
13
P1 Define
P1 terminal function setting
0
–
48
0:FX
14
P2 Define
P2 terminal function setting
0
–
48
1:RX
15
P3 Define
P3 terminal function setting
0
–
48
5:BX
16
P4 Define
P4 terminal function setting
0
–
48
27:Trv
17
P5 Define
P5 terminal function setting
0
–
48
28:Trv
Содержание SV-iS7 series
Страница 1: ......
Страница 5: ......
Страница 126: ...Basic Functions 115 Basic Functions Code Description V1 Quantizing ...
Страница 223: ...212 Peripheral Devices Group 2 ...
Страница 224: ...Peripheral Devices Peripheral Devices 213 Group 3 ...
Страница 225: ...214 Peripheral Devices Group 4 ...
Страница 231: ...220 Peripheral Devices TYPE 1 Maximum 400 Watts TYPE 2 Maximum 600 Watts ...
Страница 236: ...Safety Funtion STO Safe Torque Off Safety Funtion STO Safe Torque Off 225 10 2 1 Safety Function Wiring Diagram ...
Страница 255: ......