Table of Functions
168
Control Function Group (PAR
CON)
No.
Communi-
cation
Address
LCD Display Name
Setting Range Initial Value
Shift in
Opera-
tion
Control Mode
V
/
F
S
L
V
C
S
L
T
V
C
T
31 0h141F
S-Est P Gain2
Sensorless2 speed
estimator proportional
gain 2
1.0
–
1000.0 (%)
Dependent
on motor
capacity
O
X X X X X
32 0h1420
S-Est I Gain2 Sensorless2 speed
estimator integral gain 2 1.0
–
1000.0 (%)
Dependent
on motor
capacity
O
X X X X X
34 0h1422
SL2 OVM
Perc
Sensorless2 overvoltage
modulation range
adjustment
100
–
180 (%)
120
X
X O X X X
35 0h1423
SL2 L-
ExcitLmt
Magnetic flux current
minimum ratio
3~100[%]
10
O
X X X O X
45
Note18)
0h142D
PG P Gain
PG operation proportional
gain
0
–
9999
3000
O
O X X X X
46 0h142E
PG I Gain
PG operation integral gain 0
–
9999
50
O
O X X X X
47 0h142F
PG Slip Max% PG operation maximum
slip
0
–
200
100
X
O X X X X
48 -
ACR P Gain Current controller P gain 0
–
10000
1200
O
X O O O O
49 -
ACR I Gain
Current controller I gain 0
–
10000
120
O
X O O O O
51 0h1433
ASR Ref LPF Speed controller
reference filter
0
–
20000 (ms)
0
X
X O O X X
52 0h1434
Torque Out
LPF
Torque controller
output filter
0
–
2000 (ms)
0
X
X X X O O
53 0h1435
Torque Lmt
Src
Torque limit
setting options
0 Keypad-1
0:Keypad-1 X
X X X O O
1 Keypad-2
2 V1
3 I1
4 V2
5 I2
6 Int 485
7 Encoder
8 FieldBus
9 PLC
10 Synchro
11 Binary Type
54
Note19)
0h1436
FWD +Trq
Lmt
Forward offsetting
torque limit
0
–
200 (%)
180.0
O
X X X O O
55 0h1437
FWD
–
Trq
Lmt
Forward offsetting
torque limit
0
–
200 (%)
180.0
O
X X X O O
56 0h1438
REV +Trq Lmt Reverse regenerative
torque limit
0
–
200 (%)
180.0
O
X X X O O
57 0h1439
REV
–
Trq Lmt Reverse regenerative
torque limit
0
–
200 (%)
180.0
O
X X X O O
* The grey cells indicate a hidden code which is only visible when setting a code.
Note 18)
CON-45
–
47 are displayed when the Encoder module is installedand Control mode is
set as “
V/F
PG
”.
Note 19)
CON-54
–
57 are displayed only when DRV-
09 (Control Mode) is set as “Sensorless
-1, 2
” or
“Vector”.
In addition, the initial value of the torque limit is changed to 150% when the ADV-74
RegenAvd Level function is set.
Содержание SV-iS7 series
Страница 1: ......
Страница 5: ......
Страница 126: ...Basic Functions 115 Basic Functions Code Description V1 Quantizing ...
Страница 223: ...212 Peripheral Devices Group 2 ...
Страница 224: ...Peripheral Devices Peripheral Devices 213 Group 3 ...
Страница 225: ...214 Peripheral Devices Group 4 ...
Страница 231: ...220 Peripheral Devices TYPE 1 Maximum 400 Watts TYPE 2 Maximum 600 Watts ...
Страница 236: ...Safety Funtion STO Safe Torque Off Safety Funtion STO Safe Torque Off 225 10 2 1 Safety Function Wiring Diagram ...
Страница 255: ......