Troubleshooting and Maintenance
142
7
Troubleshooting and Maintenance
This chapter explains how to troubleshoot a problem when inverter protective functions, fault
trips, warning signals, or faults occur. If the inverter does not work normally after following the
suggested troubleshooting steps, please contact the LSIS Customer Support.
7.1
Protection Functions
7.1.1
Protection from Output Current and Input Voltage
Type
Category Details
Remarks
Over Load
Latch
Displayed when the motor overload trip is activated and the
actual load level exceeds the set level. Operates when PRT-
20 is set to any
value other than “0”.
-
Under Load
Latch
Displayed when the motor underload trip is activated and
the actual load level is less than the set level. Operates when
PRT-27 is set to any
value other than “0”.
-
Over
Current1
Latch
Displayed when the inverter output current exceeds 200%
of the rated current.
-
Over Voltage Latch
Displayed when the internal DC circuit voltage exceeds the
specified value.
-
Low Voltage Level
Displayed when the internal DC circuit voltage is less than
the specified value.
-
Ground Trip Latch
Displayed when a ground fault trip occurs on the output
side of the inverter and causes the current to exceed the
specified value. The specified value varies depending on the
inverter capacity.
-
E-Thermal
Latch
Displayed based on inverse time limit thermal
characteristics to prevent motor overheating. Operates
when PRT-40 is set to any
value other than “0”.
-
Out Phase
Open
Latch
Displayed when a 3-phase inverter output has one or more
phases in an open circuit condition. Operates when bit 1 of
PRT-
05 is set to “1”.
-
In Phase
Latch
Displayed when a 3-phase inverter input has one or more
-
Содержание SV-iS7 series
Страница 1: ......
Страница 5: ......
Страница 126: ...Basic Functions 115 Basic Functions Code Description V1 Quantizing ...
Страница 223: ...212 Peripheral Devices Group 2 ...
Страница 224: ...Peripheral Devices Peripheral Devices 213 Group 3 ...
Страница 225: ...214 Peripheral Devices Group 4 ...
Страница 231: ...220 Peripheral Devices TYPE 1 Maximum 400 Watts TYPE 2 Maximum 600 Watts ...
Страница 236: ...Safety Funtion STO Safe Torque Off Safety Funtion STO Safe Torque Off 225 10 2 1 Safety Function Wiring Diagram ...
Страница 255: ......