
Basic Functions
127
B
as
ic
Func
tio
ns
6.3
Changing the Displayed Units (Hz
↔
Rpm)
You can change the units used to display the operational speed of the inverter by setting DRV-
21 (Speed unit selection) to “0 (Hz Display)” or “1 (Rpm Display)”.
Group Code
Name
LCD Display Parameter Setting
Setting Range
Unit
DRV
21
Speed unit
selection
Hz/Rpm Sel
0
Hz Display
0
–
1
-
1
Rpm Display
6.4
Setting Multi-Step Frequency
Multi-step operations can be carried out by assigning different speeds (or frequencies) to the
Px terminals. Step 0 uses the frequency reference source set at DRV-07. Px terminal parameter
values 7 (Speed-L), 8 (Speed-M), 9 (Speed-H), and 10 (Speed-X) are recognized as binary
commands and work in combination with Fx or Rx run commands. The inverter operates
according to the frequencies set at BAS-50
–
64 (multi-step frequency 1
–
15) and the binary
command combinations.
Group Code Name
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
07
Frequency
reference source Freq Ref Src
-
-
-
BAS
50
–
64
Multi-step
frequency 1
–
15
Step Freq - x
-
-
Hz
IN
65
–
75
Px terminal
configuration
Px Define (Px: P1
–
P8 [optional: P9
–
P11]) [Optional
P9
–
P11]
7
Speed-L
0
–
51
-
8
Speed-M
-
9
Speed-H
10 Speed-X
-
89
Multi-step
command delay
time
InCheck Time
1
1
–
5000
ms
Содержание SV-iS7 series
Страница 1: ......
Страница 5: ......
Страница 126: ...Basic Functions 115 Basic Functions Code Description V1 Quantizing ...
Страница 223: ...212 Peripheral Devices Group 2 ...
Страница 224: ...Peripheral Devices Peripheral Devices 213 Group 3 ...
Страница 225: ...214 Peripheral Devices Group 4 ...
Страница 231: ...220 Peripheral Devices TYPE 1 Maximum 400 Watts TYPE 2 Maximum 600 Watts ...
Страница 236: ...Safety Funtion STO Safe Torque Off Safety Funtion STO Safe Torque Off 225 10 2 1 Safety Function Wiring Diagram ...
Страница 255: ......