Basic Functions
139
B
as
ic
Func
tio
ns
Code
Description
acc/dec commands are recognized as binary code inputs and will control the
acceleration and deceleration based on parameter values set at BAS-70
–
75
If, for example, the P7 and P8 terminals are set as XCEL-L and XCEL-M
respectively, the following operation will be available.
Acc/Dec time
P8
P7
0
-
-
1
-
2
-
3
[Multi-function terminal P7, P8 configuration]
IN-89 In Check
Time
Set the time for the inverter to check for other terminal block inputs. If IN-89
is set to 100 ms and a signal is supplied to the P6 terminal, the inverter
searches for other inputs over the next 100 ms. When the time expires, the
acc/dec time will be set based on the input received at P6.
6.8.4
Configuring Acc/Dec Time Switch Frequency
By configuring the switch frequency, you can switch between two different sets of acc/dec
times (acc/dec gradients) without configuring the multi-function terminals.
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
DRV
03
Acceleration time Acc Time
10.0
0.0
–
600.0
sec
04
Deceleration time Dec Time
10.0
0.0
–
600.0
sec
BAS
70
Multi-step
acceleration time1
Acc Time-1
20.0
0.0
–
600.0
sec
Содержание SV-iS7 series
Страница 1: ......
Страница 5: ......
Страница 126: ...Basic Functions 115 Basic Functions Code Description V1 Quantizing ...
Страница 223: ...212 Peripheral Devices Group 2 ...
Страница 224: ...Peripheral Devices Peripheral Devices 213 Group 3 ...
Страница 225: ...214 Peripheral Devices Group 4 ...
Страница 231: ...220 Peripheral Devices TYPE 1 Maximum 400 Watts TYPE 2 Maximum 600 Watts ...
Страница 236: ...Safety Funtion STO Safe Torque Off Safety Funtion STO Safe Torque Off 225 10 2 1 Safety Function Wiring Diagram ...
Страница 255: ......