Basic Functions
124
Pulse Input Setting Details
Code
Description
APO-01 Enc Opt
Mode
Sets the encoder option mode. Set APO-01 to
“
2 (Reference)
”
to receive a
pulse input for the frequency reference.
APO-04 Enc Type Sel Sets the output type.
APO-05 Enc Pulse
Sel
Selects the encoder pulse to use.
APO-06 Enc Pulse
Num
Sets the number of pulses that is appropriate for the encoder specification.
APO-09 Pulse
Monitor
Displays the pulse frequency supplied at the encoder option module when
APO-1 is set to
“
2 (Reference)
”.
APO-10 Enc Filter
Sets the time for the pulse input to reach 63% of its nominal frequency
(when the pulse frequency is supplied in multiple steps).
APO-11 Enc Pulse
x1
–
IN-96 Enc Perc
y2
Configures the gradient level and offset values for the output frequency.