Chapter 7. Inverter Parameter
85
7.2 Description on the Basic Field Bus Parameters
7.2.1 C 3 FBus ID
The allowable setting range in the inverter is 0~127. However, 0 is not used
as a station No. in CANopen. If set to o, the ERR LED will blink in the
CANopen Option. (See Section 3.2)
7.2.2 C 5 FBus LED
These parameters control the LEDs on the CANopen board.
0 Bit: CPU LED
1 Bit: ERR LED
2 Bit: NODE LED
3 Bit: BUS LED
The example of C 5 LED status)
7.2.3 C99 Comm Update
Press 1 to reflect the values set up with keypad on the CANopen Option.
7.2.4 C 4 FBus BaudRate
These parameters control the communication speed of the CANopen.
Setting range: 0~7
0: 1Mbps
1: 800Kbps
2: 500Kbps
3: 250Kbps
4: 125Kbps
5: 100Kbps
6: 50Kbps
7: 20Kbps
Default value is 0: 1Mbps.
BUS LED
(Green)
NODE LED
(Green)
ERR LED
(Red)
CPU LED
(Green)
OFF
ON
ON
ON