40
_ LS ELECTRIC
Fan and Pump
H100
EPID Function Group (EPID)
Code Comm. No
Name
LCD Display
Set Range
Default
Attribute
*
31
0h191F
EPID2 Mode selection
EPID2 Mode
0
None
0: None
O
1
Always ON
2
During Run
3
DI dependent
32
1
0h1920
EPID2 output monitor value
EPID2 Output
-100.00~100.00%
0.00
X
33
0h1921
EPID2 reference monitor value
EPID2 Ref Val
-
-
X
34
0h1922
EPID2 feedback monitor value
EPID2 Fdb Val
-
-
X
35
0h1923
EPID2 error monitor value
EPID2 Err Val
-
-
X
36
0h1924
EPID2 command source selection
EPID2 Ref Src
0
Keypad
0: KeyPad
Δ
1
V1
2
I1
3
V2
4
I2
5
RS-485
6
FieldBus
8
Pulse
9
V3
10
2
I3
37
0h1925
EPID2 keypad command value
EPID2 Ref Set
Unit Min~Unit Max
Unit Min
O
38
0h1926
EPID2 feedback source selection
EPID2 Fdb Src
0
V1
2
V2
3
I2
4
RS-485
5
FieldBus
0: V1
O
7
Pulse
8
V3
9
3
I3
39
0h1927
EPID2 P-Gain
EPID2 P-Gain
0.0~300.0 (%)
50.0
O
40
0h1928
EPID2 I-Time
EPID2 I-Time
0.0-200,0(sec)
10.0
O
41
0h1929
EPID2 D-Time
EPID2 D-Time
0,00-1,00(sec)
0.00
O
42
0h192A
EPID2 feedforward compensation gain
EPID2 FF-Gain
0.0~1000.0 (%)
0.0
O
43
0h192B
EPID2 output filter
EPID2 Out LPF
0,00-10,00(sec)
0.00
O
44
0h192C
EPID2 output high limit
EPID2 Limit Hi
EPID2 Limit Lo~100.00
100.00
O
45
0h192D
EPID2 output low limit
EPID2 Limit Lo
-100.00~EPID2 Limit Hi
0.00
O
46
0h192E
EPID2 output inversion
EPID2 Out Inv
0
No
0: No
O
1
Yes
47
0h192F
EPID2 unit
EPID2 Unit Sel
Refer to the EPID Unit table
0: CUST
O
48
0h1930
EPID2 unit scale
EPID2 Unit Scl
0
X100
2: X1
O
1
X10
2
X1
3
X0.1
4
X0.01
49
0h1931
EPID2 unit 0%
EPID2 Unit0%
X100
-30000~Unit Max
Varies according
to unit setting
O
X10
-3000.0~Unit Max
X1
-300.00~Unit Max
X0.1
-30.000~Unit Max
X0.01
-3.0000~Unit Max
50
0h1932
EPID2 unit 100%
EPID2 Unit100%
X100
Unit Min~30000
Varies according
to unit setting
O
X10
Unit Min~3000.0
X1
Unit Min~300.00
X0.1
Unit Min~30.000
X0.01
Unit Min~3.0000
1
EPID-32~EPID-50 codes appear when EPID-31 code is not 0(None).
2
‘9(V3)~10(I3)’ of EPID-36 are available when Extension IO option is equipped. Refer to Extension IO option manual for more detail information.
3
‘8(V3)~9(I3)’ of EPID-38 are available when Extension IO option is equipped. Refer to Extension IO option manual for more detail information