30
_ LS ELECTRIC
Fan and Pump
H100
Output Terminal Block Function Group (OUT)
Code Comm. No.
Name
LCD Display
Set Range
Default
Attribute
*
71
0h1547
P7 terminal function setting
P7 Define
19
Up
9:Sp-H
Δ
20
Down
22
U/D Clear
23
Analog Hold
24
I-Term Clear
25
PID Openloop
26
PID Gain2
27
PID Ref Change
28
2nd Motor
29
Interlock 1
30
Interlock 2
31
Interlock 3
32
Interlock 4
33
Interlock 5
34
Pre Excite
35
Timer In
37
dis Aux Ref
38
FWD JOG
39
REV JOG
40
Fire Mode
41
EPID1 Run
42
EPID1 ItermClr
43
Time Event En
44
Pre Heat
45
Damper Open
46
PumpClean
47
EPID2 Run
48
EPID2 ItermClr
49
Sleep Wake Chg
50
PID Step Ref L
51
PID Step Ref M
52
PID Step Ref H
53
1
Interlock6
54
Interlock7
55
Interlock8
83
0h1553
DI On Delay Selection
DI On DelayEn
000 0000 ~ 111 1111
111 1111
Δ
84
0h1554
DI Off Delay Selection
DI Off DelayEn
000 0000 ~ 111 1111
111 1111
Δ
85
0h1555
Multifunction input terminal on filter
DI On Delay
0-10000(msec)
10
O
86
0h1556
Multifunction input terminal off filter
DI Off Delay
0-10000(msec)
3
O
87
0h1557
Multifunction input contact point selection
DI NC/NO Sel
P7-P1
000 0000
Δ
0
A Contact Point(NO)
1
B Contact Point(NC)
89
0h1559
Multi-step command delay time
InCheck Time
1-5000(msec)
1
Δ
90
0h155A
Multifunction input terminal status
DI Status
P7-P1
000 0000
O
0
Open (Off)
1
Access (On)
91
0h155B
Pulse input display
Pulse Monitor(kHz)
0.00~50.00(kHz)
0.00
X
92
0h155C
TI input filter constant time
TI Filter
0-9999(msec)
10
O
93
0h155D
TI input minimum pulse
TI Pls x1
0~TI Pls x2
0.00
O
94
0h153E
Output % at TI minimum pulse
TI Perc y1
0.00~100.00(%)
0.00
O
95
0h155F
TI input maximum pulse
TI Pls x2
0,00-32,00(kHz)
32.00
O
96
0h1560
Output % at TI maximum pulse
TI Perc y2
0~100(%)
100.00
O
97
0h1561
Changing TI rotation direction
TI Inverting
0
No
0: No
O
1
Yes
98
0h1562
TI quantizing level
TI Quantizing
0.00
2
,0.04~10.00(%)
0.04
O
1
53(Interlock6)~55(Interlock8)’ of IN-65~71 are available when Extension IO option is equipped. Refer to Extension IO option manual for more detail
information
2
Quantizing is disabled if ‘0’ is selected.
Содержание H100 Series
Страница 1: ...3 phase 200 240V 0 75 18 5kW 3 phase 380 480V 0 75 500kW Fan and Pump Drive H100 ...
Страница 81: ...H100 _ 81 EnergySavingDrive Memo ...
Страница 82: ...82_ LS ELECTRIC FanandPumpH100 Memo ...
Страница 83: ...H100 _ 83 EnergySavingDrive Memo ...