H100 _
39
Energy Saving Drive
EPID Function Group (EPID)
1
Code Comm. No
Name
LCD Display
Set Range
Default
Attribute
*
00
-
Jump code
Jump Code
1~99
1
O
01
0h1901
EPID1 Mode selection
EPID1 Mode
0
None
0: None
O
1
Always ON
2
During Run
3
DI dependent
02
2
0h1902
EPID1 output monitor value
EPID1 Output
-100.00~100.00%
0.00
X
03
0h1903
EPID1 reference monitor value
EPID1 Ref Val
-
-
X
04
0h1904
EPID1 feedback monitor value
EPID1 Fdb Val
-
-
X
05
0h1905
EPID1 error monitor value
EPID1 Err Val
-
-
X
06
0h1906
EPID1 command source selection
EPID1 Ref Src
0
Keypad
0: KeyPad
Δ
1
V1
3
V2
4
I2
5
Int 485
6
FieldBus
8
Pulse
9
3
V3
10
I3
07
0h1907
EPID1 keypad command value
EPID1 Ref Set
Unit Min~Unit Max
Unit Min
O
08
0h1908
EPID1 feedback source selection
EPID1 Fdb Src
0
V1
0: V1
O
2
V2
3
I2
4
Int485
5
FieldBus
7
Pulse
8
4
V3
9
I3
09
0h1909
EPID1 P-Gain
EPID1 P-Gain
0.00~300.00(%)
50.00
O
10
0h190A
EPID1 I-Time
EPID1 I-Time
0.0-200,0(sec)
10.0
O
11
0h190B
EPID1 D-Time
EPID1 D-Time
0,00-1,00(sec)
0.00
O
12
0h190C
EPID1 feedforward compensation gain
EPID1 FF-Gain
0.0~1000.0 (%)
0.0
O
13
0h190D
EPID1 output filter
EPID1 Out LPF
0,00-10,00(sec)
0.00
O
14
0h190E
EPID1 output high limit
EPID1 Limit Hi
EPID1 Limit Lo ~100.00
100.00
O
15
0h190F
EPID1 output low limit
EPID1 Limit Lo
-100.00-Lím Alto EPID2
0.00
O
16
0h1910
EPID1 output inversion
EPID1 Out Inv
0
No
0: No
O
1
Yes
17
0h1911
EPID1 unit
EPID1 Unit Sel
Refer to the EPID Unit table
1: %
O
18
0h1912
EPID1 unit scale
EPID1 Unit Scl
0
X100
2: X1
O
1
X10
2
X1
3
X0.1
4
X0.01
19
0h1913
EPID1 unit 0%
EPID1 Unit0%
X100
-30000~Unit Max
Varies according
to unit setting
O
X10
-3000.0~Unit Max
X1
-300.00~Unit Max
X0.1
-30.000~Unit Max
X0.01
-3.0000~Unit Max
20
0h1914
EPID1 unit 100%
EPID1 Unit100%
X100
Unit Min~30000
Varies according
to unit setting
O
X10
Unit Min~3000.0
X1
Unit Min~300.00
X0.1
Unit Min~30.000
X0.01
Unit Min~3.0000
1
EPID Group is displayed when PID-02 code is set to 'Yes'.
2
EPID-02~EPID-20 codes appear when EPID-01 code is not 0(None).
3
‘9(V3)~10(I3)’ of EPID-06 are available when Extension IO option is equipped. Refer to Extension IO option manual for more detail information.
4
‘8(V3)~9(I3)’ of EPID-08 are available when Extension IO option is equipped. Refer to Extension IO option manual for more detail information.