H100 _
55
Energy Saving Drive
Vacuum Pump (MC6) Group
Macro Code
Code
LCD Display
Default
0
-
Jump Code
1 : CODE
1
DRV 3
Acc Time
0.75~90kW
30.0
110~250kW
90.0
315~500kW
150.0
2
DRV 4
Dec Time
0.75~90kW
60.0
110~250kW
180.0
315~500kW
300.0
3
DRV 7
Freq Ref Src
1: Keypad-2
4
DRV 9
Control Mode
1: Slip Compen
5
DRV 11
JOG Frequency
20.00
6
DRV 12
JOG Acc Time
30.0
7
DRV 13
JOG Dec Time
60.0
8
DRV 15
Torque Boost
1: Auto1
9
BAS 7
V/F Pattern
1: Square
10
BAS 70
Acc Time-1
30.0
11
BAS 71
Dec Time-1
50.0
12
BAS 72
Acc Time-2
32.0
13
BAS 73
Dec Time-2
52.0
14
BAS 74
Acc Time-3
34.0
15
BAS 75
Dec Time-3
54.0
16
BAS 76
Acc Time-4
36.0
17
BAS 77
Dec Time-4
56.0
18
BAS 78
Acc Time-5
38.0
19
BAS 79
Dec Time-5
58.0
20
BAS 80
Acc Time-6
40.0
21
BAS 81
Dec Time-6
59.0
22
BAS 82
Acc Time-7
42.0
23
BAS 83
Dec Time-7
60.0
24
ADV 10
Power-on Run
1: Yes
25
ADV 25
Freq Limit Lo
40.00
26
ADV 64
FAN Control
2: Temp Control
27
ADV 65
U/D Save Mode
1: Yes
28
CON 4
Carrier Freq
3.0
29
CON 70
SS Mode
0: Flying Start-1
30
CON 77
KEB Select
1 : Yes
Macro Code
Code
LCD Display
Default
31
OUT 32
Relay 2
14: Run
32
PID 1
PID Sel
1 : Yes
33
PID 3
PID Output
-
34
PID 4
PID Ref Value
-
35
PID 5
PID Fdb Value
-
36
PID 10
PID Ref 1 Src
4: I2
37
PID 11
PID Ref 1 Set
5.000
38
PID 25
PID P-Gain 1
50.00
39
PID 26
PID I-Time 1
2.5
40
PID 50
PID Unit Sel
5: inWC
41
PID 51
PID Unit Scale
3: x0.1
42
AP1 21
Pre-PID Freq
30.00
43
PRT 8
RST Restart
11
44
PRT 9
Retry Number
3
45
PRT 10
Retry Delay
4.0
46
PRT 11
Lost KPD Mode
3: Dec
47
PRT 12
Lost Cmd Mode
3:Hold npvt
48
PRT 40
ETH Trip Sel
1: Free Run
49
PRT 42
ETH 1min
120
50
PRT 52
Stall Level 1
130
51
PRT 60
PipeBroken Sel
1: Warning
52
PRT 61
PipeBroken Lev
90.0
53
PRT 62
Pipe Broken DT
22.0
54
PRT 66
DB Warn %ED
10
55
PRT 70
LDT Sel
1: Warning
56
PRT 72
LDT Source
0: Output Input
57
PRT 75
LDT Band Width
10% of max. value of LDT source
58
PRT 76
LDT Freq
15.00
59
PRT 77
LDT Restart DT
100.0
60
M2 4
M2-Acc Time
10.0
61
M2 5
M2-Dec Time
20.0
62
M2 8
M2-Ctrl Mode
1: Slip Compen
63
M2 25
M2-V/F Patt
1: Square
64
M2 28
M2-Stall Lev
125
65
M2 29
M2-ETH 1min
120
Constant Torque(MC7) Group
Macro Code
Code
LCD Display
Default
0
-
Jump Code
1 : CODE
1
DRV 3
Acc Time
0.75~90kW
30.0
110~250kW
90.0
315~500kW
150.0
2
DRV 4
Dec Time
0.75~90kW
20.0
110~250kW
60.0
315~500kW
100.0
3
DRV 7
Freq Ref Src
1: Keypad-2
4
DRV 9
Control Mode
1: Slip Compen
5
DRV 12
JOG Acc Time
10.0
6
DRV 13
JOG Dec Time
20.0
7
DRV 15
Torque Boost
1: Auto1
8
BAS 70
Acc Time-1
10.0
9
BAS 71
Dec Time-1
20.0
10
BAS 72
Acc Time-2
12.5
11
BAS 73
Dec Time-2
22.5
12
BAS 74
Acc Time-3
15.0
13
BAS 75
Dec Time-3
25.0
14
BAS 76
Acc Time-4
17.5
15
BAS 77
Dec Time-4
27.5
16
BAS 78
Acc Time-5
20.0
17
BAS 79
Dec Time-5
30.0
18
BAS 80
Acc Time-6
22.5
19
BAS 81
Dec Time-6
32.5
Macro Code
Code
LCD Display
Default
20
BAS 82
Acc Time-7
25.0
21
BAS 83
Dec Time-7
35.0
22
ADV 1
Acc Pattern
1: S-curve
23
ADV 2
Dec Pattern
1: S-curve
24
ADV 25
Freq Linit Lo
20.00
25
ADV 74
RegenAvd Sel
1: Yes
26
CON 4
Carrier Freq
3.0
27
CON 70
SS Mode
0: Flying Start-1
28
CON 77
KEB Select
1: Yes
29
OUT 32
Relay 2
14: Run
30
API 21
Pre-PID Freq
30.00
31
API 22
Pre-PID Delay
120.0
32
PRT 12
Lost Cmd Mode
2: Dec
33
PRT 40
ETH Trip Sel
2: Dec
34
PRT 66
DB Warn %ED
10
35
PRT 70
LDT Sel
1: Warning
36
PRT 72
LDT Source
0: Output Current
37
PRT 75
LDT Band Width
10% of max. value of LDT source
38
PRT 76
LDT Freq
5.00
39
PRT 77
LDT Restart DT
250.0
40
M2 4
M2-Acc Time
10.0
41
M2 5
M2-Dec Time
20.0
42
M2 8
M2-Ctrl Mode
1: Slip Compen