May, 2013
Page 38 of 52
949-1194 Rev. 7
If
A L 1
is set to
O F F
goto
A L 2
(next page).
If
A L 1
is set to
E U n t
, go to
A 1 S t
below.
A 1 t
Alarm 1 Type: Select
A b S
or
d E
A b S
Absolute Alarm that may be set anywhere within the values of
S C A L
and
S C A H
and is independent of
S P 1
.
d E
Deviation Alarm that may be set as an offset from
S P 1
. As
S P 1
is
changed the Alarm Point will track with
S P 1
. A deviation alarm will also
track any active ramp or soak set point.
A 1 r E
Alarm 1 Reset: Select
O n O F
or
H o l d
.
O n O F
Automatic Reset.
H o l d
Manual Reset. Reset (acknowledge) by simultaneously pressing the
INDEX
&
DOWN ARROW
keys for 3 seconds.
A 1 P i
Alarm 1 Power Interrupt: Select
O n
or
O F F
.
O n
Alarm Power Interrupt is
O n
.
O F F
Alarm Power Interrupt is
O F F
.
A 1 i H
Alarm 1 Inhibit: Select
O n
or
O F F
.
O n
Alarm Inhibit is
O n
. Alarm action is suspended until the process value
first enters a non-alarm condition.
O F F
Alarm Inhibit is
O F F
.
A 1 S t
Alarm 1 Output State: Select
C L O S
or
O P E n
.
C L O S
Closes Contacts at Alarm Set Point.
O P E n
Opens Contacts at Alarm Set Point.
A 1 L P
Alarm 1 Lamp: Select
O o n
or
O o F F
.
O o n
Alarm Lamp is ON when alarm contact is closed.
O o F F
Alarm Lamp is OFF when alarm contact is closed.
A 1 L b
Alarm 1 Loop Break. Select
O n
or
O F F
.
O n
Loop Break Condition will cause an Alarm Condition.
O F F
Loop Break will not affect the Alarm Condition.
A L 2
Alarm 2 function: Select
O F F
,
L o
,
H i
,
H i L o
, or
E U n t
.
O F F
Alarm 2 is disabled. No Alarm 2 menu items appear in the Secondary or
Secure menus.
L o
Low Alarm Only.
A 2 L o
appears in the Secondary Menu.
H i
High Alarm Only.
A 2 H i
appears in the Secondary Menu.
H i L o
High and Low Alarms. Both
A 2 L o
and
A 2 H i
appear in the Secondary
Menu, and share the same Alarm Relay output.
E U n t
Alarm 2 is controlled by the Ramp/Soak program function. See pages
15-18 and 29 (#
A 2
) for further information.