AUTOSET guided configuration
When a factory-new soft starter is first powered up, the
AUTOSET
configuration wizard launches, to simplify and speed up the configuration and commissioning of the device.
This procedure consists in prompting the user for 4 simple items of information, which enable the ADXL to configure itself with the values most probably suited to the installation in
question.
In any case, once the
AUTOSET
procedure has completed, an expert user can fine tune these settings in programming mode.
The system prompts the user for the following information, in sequence:
STEP
INFORMATION
DEFAULT
RANGE
1
Display language
ENG
ENG-ITA-FRA-ESP-POR-DEU
2
Nominal motor current
100% ADXL rating
Example: for ADXL0030600
30.0A
50…100% ADXL rating
Example: for ADXL0030600
15.0….30.0A
3
Type of starter application
General purpose
General purpose (GP)
Centrifugal pump
Fire fighting pump
Belt conveyor
Fan
Mixer
4
Starter duty level
Normal
Light (e.g. low inertia, no load starting): 3.5 I
e
Normal: 4.5 I
e
Heavy (e.g. high inertia or loaded starting): 5.5 I
e
AUTOSET
START
1
LANGUAGE
ENG
ITA
FRA
ESP
POR
DEU
STOP
-
START
+
NEXT
▼
2
CURRENT
15A
…
30A
STOP
-
START
+
NEXT
▼
3
APPLICATION
GENERAL PURPOSE
CENTRIFUGAL PUMP
FIRE FIGHTING PUMP
BELT CONVEYOR
FAN
MIXER
STOP
-
START
+
NEXT
▼
4
DUTY LEVEL
LIGHT
NORMAL
HEAVY
STOP
-
START
+
NEXT
▼
SAVE?
END
AUTOSET
CONFIGURATION
START
QUIT
WITHOUT
CONFIGURATION
STOP
-