P03.01

 - If set to OFF, password management is deactivated; access to settings and the control menu is free. 

P03.02 

- With P03.01 active, value to be specified to activate user level access. See the 

Password protected access

 chapter. 

P03.03 

- As P03.02, referred to Advanced level access. 

P03.04 

- If set to a numeric value, it becomes the code to be specified via serial communication line before being able to send remote controls. 

  

 

 

P04 – PROTECTIONS 

UoM 

Default 

Range 

P04.01 

Enable motor thermal protections  

 

ON 

OFF / ON 

P04.02 

Starting thermal protection class 

 

10 

 2  

10A 

 10  
 15  
 20  
 25  
 30 
 35  

40 

P04.03 

Run thermal protection class  

 

10 

 2  

 10A  

 10  
 15 
 20 
 25  
 30 

P04.04 

Motor thermal protection reset 

120 

0…140 

P04.05 

Terminal IN3 mode 

 

Digital DIGITAL 

 

 PTC 

P04.06 

Number of automatic alarm reset attempts 

 

OFF 

OFF / 1…6 

P04.07 

Automatic alarm reset interval 

min 

1…30 

P04.08 

Minimum torque threshold (load too low) 

%Tn 

OFF 

OFF / 20…100 

P04.09 

Minimum torque trip delay 

sec 

10 

1…20 

P04.10 

Starting time out 

sec 

OFF 

OFF / 10…1000 

P04.11 

Phase sequence check 

 

OFF 

OFF  

 L1-L2-L3  
 L3-L2-L1 

P04.12 

Minimum voltage threshold 

OFF 

OFF / 170…760 

P04.13 

Minimum voltage trip delay 

sec 

0…600 

P04.14 

Maximum voltage threshold 

OFF 

170…760 / OFF 

P04.15 

Maximum voltage trip delay 

sec 

0…600 

P04.16 

Current asymmetry  

OFF 

OFF / 1…25 

P04.17 

Current asymmetry delay 

sec 

0…600 

P04.18 

Maintenance interval 

OFF 

OFF / 0…50,000 

P04.19 

Alarm reset command 

 

STOP STOP 

START 

STA-STO 

P04.01 – 

General enabling of thermal protections set with parameters P04.02 and P04.03.  If this parameter is set to OFF (for example, for starting multiple motors with a single 

starter) both protections will be disabled.

 

P04.02 – P04.03

 - Define the motor electronic thermal protection class, for the starting and run phases respectively. The thermal protection class is set in relation to the type of 

use of the motor. Class 10 is adapted to normal use, classes 15, 20 etc. for heavier duty use. If the motor has a heavy duty application, for more effective protection you 
can set the starting protection class higher than the run protection class.

  

P04.04 – 

Determines the value of the thermal status beneath which the motor thermal protection alarm is reset.

 

P04.05 – 

Defines whether terminal IN3 is used as a digital input or as PTC sensor input. 

P04.06 – 

This function is used in unsupervised applications with 2-wire motor starting command. If the motor is stopped by an alarm with ‘Automatic reset’ enabled, after a time 

defined in P04.07 the alarm resets and hence the motor starts again. If after the reset the motor does not restart, a number of motor reset and restarting attempts are 
made as set. During the alarm status, the display alternates the active alarm and the time remaining to the automatic reset. 

P04.07 – 

Delay between successive automatic reset attempts. 

P04.08 –

 Normally used as protection against pumps dry running or to detect failure of transmission chains or belts. When the torque is lower than this setting, after the delay set 

in P04.09 the alarm 

A09 Load too low

 is generated. The trip delay is reset  if the torque returns to a value of 10% higher than the setting. 

P04.09 – 

Load too low alarm trip delay. 

P04.10 – 

Checks that the motor starting process does not exceed the set time, i.e. that the mechanical assemblies have not been modified (due to wear or failure) in such a way 

that prevents the machine from starting properly. A starting time longer than this setting trips alarm 

A10 Starting time too long

P04.11 – 

Enables control of the power phase sequence, i.e. the direction of rotation of the motor. Setting L1-L2-L3 corresponds to forwards rotation, L3-L2-L1 to reverse. A 

sequence other than that specified trips alarm 

A03 Incorrect phase sequence

P04.12 – P04.13 – 

A voltage lower than P04.12 for longer than the time P04.13 trips alarm 

A19 Line voltage too low

P04.14 – P04.15 – 

A voltage higher than P04.14 for longer than the time P04.15 trips alarm 

A20 Line voltage too 

high. 

P04.16 – P04.17 – 

Controls the current asymmetry during full voltage running. Asymmetry greater than the setting for a time longer than P04.17 trips alarm 

A06 Current 

asymmetry

.

 

P04.18 – 

Generates alarm 

A22 Maintenance request 

when the motor exceeds the set number of hours of operation. This is reset with the command 

C01 Reset maintenance 

counter

 which simultaneously restores the hour meter. 

P04.19 – 

Defines the origin of the alarms reset command. 

STOP

 = The alarms are reset when the STOP input opens. 

START

 = The alarms are reset when the START input 

closes. 

STA-STO

 = Both of the above.

 

 

 

P05 - MISCELLANEOUS 

 

Default 

Range 

P05.01 

Torque control 

 

ON 

ON 

OFF 

P05.02 

Torque linearisation coefficient  

 

100 

50…150% 

P05.03 

Maximum torque limitation 

 

OFF 

OFF / 10…200%Tn 

P05.04 

Main RS-485 function 

 

SLAVE SLAVE 

REM EXP 

Содержание ADXL 0030 600

Страница 1: ... or solvents Contents Page Description 2 Front button functions 2 Front LEDs 2 Display indications 2 AUTOSET guided configuration 3 Navigating the display pages 4 Operational status 4 Remote keypad 4 Startup methods 5 Protections 5 Motor thermal protection 6 Motor thermal protection via PTC 6 Starter thermal protection 6 Main menu 7 Password protected access 7 Inputs outputs internal variables 7 L...

Страница 2: ...lay indication and alarm pre alarm thresholds Advanced self diagnostics NFC interface for programming with smartdevice Front mounted optical interface for programming and maintenance Isolated RS485 interface optional mounted in a dedicated slot with Modbus protocol Alarms with language specific messages and user programmable properties Compatible with the SAM1 App NFC App Synergy supervision softw...

Страница 3: ...ion in sequence STEP INFORMATION DEFAULT RANGE 1 Display language ENG ENG ITA FRA ESP POR DEU 2 Nominal motor current 100 ADXL rating Example for ADXL0030600 30 0A 50 100 ADXL rating Example for ADXL0030600 15 0 30 0A 3 Type of starter application General purpose General purpose GP Centrifugal pump Fire fighting pump Belt conveyor Fan Mixer 4 Starter duty level Normal Light e g low inertia no load...

Страница 4: ... does not press the navigation keys to view values the text bar indicates the starter s status The possible statuses are given in the following table with their explanations STATUS DISPLAY DESCRIPTION Line absent NO POWER No power to terminals L1 L2 L3 Starter ready READY Power present starter ready to run Start delay xx DELAY XX Delay applicable to the current start command A countdown displays S...

Страница 5: ...ing a less gradual acceleration than the torque ramp Together with these two starting methods there is the maximum starting current limitation function o Current limit P01 02 If the current delivered by the highest of the three phases reaches or exceeds the set limit the ADXL reduces its voltage on the motor so as to remain below the maximum limit setting P01 02 This behaviour has priority over bo...

Страница 6: ...maximum value which is 140 and trips alarm A14 Motor thermal protection The trip time is shown in the tables given below as a function of the overload current The curves for the various graphs refer to the curve selected with parameters P04 02 and P04 03 The cold trip curves indicate the trip time starting from thermal status 0 while the hot trip curves start from thermal status 100 With the motor...

Страница 7: ...mmunication ports 1 Like the inputs outputs there are internal variables bit which may be associated to the outputs or combined For example limit thresholds can be applied to the measurements performed by the system voltage current etc In this case the internal variable named LIMx will be activated when the measurement is beyond the limits defined by the user by means of the respective setting men...

Страница 8: ... the text of the message which must appear on the display when the condition occurs 3 the properties of the alarm like for the standard alarms i e so as to interact with the genset control For example going beyond a threshold may be a condition which generates the alarm In this case the source must be one of the LIMx limit thresholds If instead the alarm must be displayed as a consequence of the a...

Страница 9: ...measurements set parameters download events and send collected data via e mail Parameter setting from smartphone or tablet with NFC You can use the Lovato Electric NFC App available for Android tablets and smartphones to program the parameters in a simple intuitive manner without the need for cables and even with the ADXL powered off Simply place the smart device against the ADXL s front panel to ...

Страница 10: ...must be set in such a way that the motor starts running slowly immediately after the start command P01 04 With torque control enabled P05 01 ON this parameters determines the time required to reach 100 motor torque and thus sets the acceleration ramp slope If the torque demand from the load is less than 100 the time required to deliver it will be shorter in proportion to keep the slope constant If...

Страница 11: ...l input or as PTC sensor input P04 06 This function is used in unsupervised applications with 2 wire motor starting command If the motor is stopped by an alarm with Automatic reset enabled after a time defined in P04 07 the alarm resets and hence the motor starts again If after the reset the motor does not restart a number of motor reset and restarting attempts are made as set During the alarm sta...

Страница 12: ... Selected input contact closing delay P06 n 05 Selected input contact opening delay P07 PROGRAMMABLE OUTPUTS OUTn n 1 3 UoM Default Range P07 n 01 Output function OUT1 ALL GLB OUT2 LIN CONT OUT3 RUN see Output functions table P07 n 02 Function index x 1 1 8 P07 n 03 Normal status OFF OFF ON P07 n 04 ON delay sec 0 0 0 6000 0 P07 n 05 OFF delay sec 0 0 0 6000 0 Note This menu is divided into 3 sect...

Страница 13: ...eshold remains stored and must be manually reset using the control menu ON or whether it resets automatically OFF P13 USER ALARMS UAn n 1 4 Default Range P13 n 01 Reference value OFF OFF INPx OUTx LIMx REMx P13 n 02 Channel no x 1 OFF 1 99 P13 n 03 Function UAn text 16 characters Note this menu is divided into 4 sections for user alarms UA1 4 P13 n 01 This defines the digital input or internal var...

Страница 14: ... bypass A09 MOTOR LOAD TOO LOW Motor load torque lower than setting during bypass A10 STARTING TOO LONG Starting time from start to bypass longer than setting A11 BYPASS RELAY FAULT Bypass relay contacts did not close or open A12 MOT THERMAL WARNING Imminent motor protection trip with motor in bypass A13 STARTER TH WARNING Imminent soft starter protection trip A14 MOTOR THERMAL TRIP Motor thermal ...

Страница 15: ...input Used as a source for user alarms for instance 11 CONTROL Runs the Cx commands menu The number of the command to be executed is x set in P06 n 02 Programmable inputs default settings The following table gives the factory default settings for the programmable inputs If necessary these settings can be changed with menu P06 Programmable inputs INPUT TERMINALS DEFAULT FUNCTION INP1 IN1 START INP2...

Страница 16: ...ST LOW POWER MOTOR ADVANCED Test with low power motor Ignores current related alarms for a bench test with low power motors Installation Recommendations Switch off power to the soft starter every time you need to work on the electrical or mechanical equipment of the system or machine A disconnecting device such as switch disconnector line contactor etc must always be included to cut off the power ...

Страница 17: ...485 communications interface code EXC1042 2 wire starting Motor PTC connection Starting with reversible rotation Timer delayed at de energisation code TMD 2 T1 1 L1 4 T2 6 T3 3 L2 5 L3 A1 FU1 QF1 PROG OUT A2 A1 QS2 11 14 12 21 24 34 FAN FAN C IN1 IN2 IN3 PROG IN KM1 A B RS485 OUT1 OUT2 OUT3 2 KM1 KM2 KM2 KM1 SB4 SB2 KM2 KM1 OUT2 KM2 SB2 SB4 KM1 KM2 T1 ...

Страница 18: ...Doc I456GB06_16 docx 29 06 2016 p 18 20 Mechanical dimensions ADXL0030 ADXL0045 ADXL0060 ADXL0075 ADXL0085 ADXL0115 Terminal layout A1 A2 11 14 12 21 24 34 C IN1 IN2 IN3 FAN ...

Страница 19: ... FWP 80B 80FE ADXL 0045 600 125 5 600 FWP 125A 120FEE ADXL 0060 600 160 5 600 FWP 150A 160FEE ADXL 0075 600 250 10 600 FWP 175A 180FEE ADXL 0085 600 315 10 600 FWP 200A 200FEE ADXL 0115 600 400 10 600 FWP 250A 250FM ADXL 0135 600 450 10 600 FWP 300A 315FM ADXL 0162 600 500 10 600 FWP 500A 500FMM ADXL 0190 600 630 10 600 FWP 600A 630FMM ADXL 0250 600 700 18 600 FWP 700A 700FMM ADXL 0320 600 800 18 ...

Страница 20: ...g IEC EN 60068 2 27 Vibration resistance 0 7g IEC EN 60068 2 6 Supply relay connections Terminal types Screw type fixed Wire cross section min and max 0 2 4 mm2 26 10 AWG Tightening torque 0 8 Nm 7 lbin Fan supply and digital input connections Terminal types Screw type fixed Wire cross section min and max 0 2 2 5 mm2 24 12 AWG Tightening torque 0 44 Nm 4 lbin Power connections Terminal types Fixed...

Отзывы: