Table of alarms
The following table shows the alarm codes, together with a description and the default properties of each one.
CODE
Description
Enabled
Re
ta
in
in
g
Gl
obal
al
ar
m
St
op mot
or
Decel
er
ati
on
Auto r
eset
Inhi
bi
t
No LCD
A01
NO POWER LINE
A02
PHASE LOSS
A03
WRONG PHASE SEQUENCE
A04
FREQUENCY OUT LIMITS
A05
AUX POWER FAILURE
A06
CURRENT ASYMMETRY
A07
OVERCURRENT TRIP
A08
LOCKED ROTOR
A09
MOTOR LOAD TOO LOW
A10
STARTING TOO LONG
A11
BYPASS RELAY FAULT
A12
MOT. THERMAL WARNING
A13
STARTER TH. WARNING
A14
MOTOR THERMAL TRIP
A15
STARTER THERMAL TRIP
A16
PHASE L1-T1 SHORTED
A17
PHASE L3-T3 SHORTED
A18
TEMP. SENSOR FAULT
A19
LINE VOLTAGE TOO LOW
A20
LINE VOLTAGE TOO HIGH
A21
MOTOR CURRENT TOO LOW
A22
MAINTENANCE REQUEST
A23
COOLING FAN FAULT
A24
COOLING FAN LOCKED
UA1..4
User alarm
Alarm disabled by default for ADXL0030..ADXL0115 and enabled by default for ADXL 0135..ADXL0320
Description of the alarms
CODE
DESCRIPTION
REASON FOR THE ALARM
A01
NO POWER LINE
All three phases not present when start command given.
A02
PHASE LOSS
One phase not present when start command given or when motor is running.
A03
WRONG PHASE SEQUENCE
Phase sequence does not match setting.
A04
FREQUENCY OUT LIMITS
Frequency of line voltage outside of +-5% tolerance around 50 or 60Hz.
A05
AUX POWER FAILURE
Voltage too low or micro interruption longer than the allowed one.
A06
CURRENT ASYMMETRY
When the motor is running, current asymmetry greater than setting for time longer than setting.
A07
OVERCURRENT TRIP
Current >750%Ie (starter current) for
200msec during starting.
A08
LOCKED ROTOR
Current >500%In (nominal motor current) for
200msec during bypass.
A09
MOTOR LOAD TOO LOW
Motor load torque lower than setting during bypass.
A10
STARTING TOO LONG
Starting time (from start to bypass) longer than setting.
A11
BYPASS RELAY FAULT
Bypass relay contacts did not close or open.
A12
MOT. THERMAL WARNING
Imminent motor protection trip with motor in bypass.
A13
STARTER TH. WARNING
Imminent soft starter protection trip.
A14
MOTOR THERMAL TRIP
Motor thermal protection tripped (inside starter or via PTC input).
A15
STARTER THERMAL TRIP
Heatsink temperature greater than maximum allowed value.
A16
PHASE L1-T1 SHORTED
SCR in short circuit or bypass contactor contacts welded.
A17
PHASE L3-T3 SHORTED
SCR in short circuit or bypass contactor contacts welded.
A18
TEMP. SENSOR FAULT
NTC internal temperature sensor for starter heatsink interrupted or broken.
A19
LINE VOLTAGE TOO LOW
Line voltage L1-L3 lower than setting for set time.
A20
LINE VOLTAGE TOO HIGH
Line voltage L1-L3 higher than setting for set time.
A21
MOTOR CURRENT TOO LOW
Motor current <10%In (In = set nominal motor current) for all three phases.
A22
MAINTENANCE REQUEST
Maintenance interval expired.
A23
COOLING FAN FAULT
No fans detected.
A24
COOLING FAN LOCKED
Fan current too high, rotor probably jammed.
A25
SYSTEM ERROR
Internal error. Please contact Lovato Electric customer service.
UA1..4
USER ALARM
The user alarm was generated by the activation of the variable or of the associated input by means of menu P13.
Programmable input functions table
The following table shows all the functions which can be associated to the programmable digital inputs INPn.
Each input may be set so as to have inverted function (NO - NC), with energising or de-energising delay with independent set times.
Some functions require a further numeric parameter defined by index (x) specified by parameter
P06.n.02
.
See menu P06
Programmable inputs
for further details.
NO.
FUNCTION
DESCRIPTION