LOVATO ELECTRIC RGK 50 Скачать руководство пользователя страница 7

 

 

                                                                                                                                                                              p. 7 / 25

 

Расширенное меню 

 

Advanced menu

 

 

“01” 

УСТАНОВКИ

 (

ЯЗЫКИ

По

 

у мо л ч

Пределы 

“01” UTILITY (LANGUAGES) 

 

 

 

 

P0101 Языки 

English 

English/Italiano/ Français/ 

Portugues/Espanol

 

P0101 Languages 

P0102 Год 

2001 

1989-2089 

P0102 Year 

P0103 Месяц 

1-12 

P0103 Month

 

P0104 День месяца 

1-31 

P0104 Day of the month

 

P0105 День недели 

1-7 

P0105 Day of the week

 

P0106 Часы 

0-23 

P0106 Hour

 

P0107 Минуты 

0-59 

P0107 Minutes

 

P0108 Секунды 

0-59 

P0108 Seconds

 

P0109 Установка часов при запуске 

ON 

OFF/ON 

P0109 Clock setting at power-up

 

P0110 Время возврата к основной странице (sec) 

60 

OFF/5-999 

P0110 Page return default (sec)

 

P0111 Контраст дисплея (%) 

40 

0-100 

P0111 Display contrast (%) 

P0112 Яркость дисплея (%) 

65 

0-100 

P0112 Display backlight (%) 

P0113 Время отключения подсветки (sec) 

60 

OFF/1-900 

P0113 Delay to switch off backlight (sec) 

 

“02” ОСНОВНОЕ 

По

 

у мо л ч

Пределы 

“02” GENERAL 

 

 

 

 

P0201 CT коэффициент трансформатора 

1.0 

1.0-2000.0 

P0201 CT ratio

 

P0202 VT коэффициент трансформатора 

1.0 

1.0-500.0 

P0202 VT ratio

 

P0203 Тип электрической сети 

3N 

3N-3-2N-1N 

P0203 Wiring configuration

 

P0204 Номинальное напряжение (V) 

400 

100-50000 

P0204 Rated voltage (V)

 

P0205 Частота (Hz) 

50 

50/60 

P0205 Frequency (Hz)

 

P0206 RPM / “W” соотношение   

(1)

 

1.000 

0.001-50.000 

P0206 RPM / “W” ratio   

(1)

 

P0207 Скорость вращения вала (RPM) 

1500 

750-3600 

P0207 Rated engine speed (RPM)

 

P0208 Единицы измерения 

°C 

bar 

°C/°F 

bar/psi 

l/gal 

P0208 Unit of measure 

P0209 MAINS/GEN задержка сигнала вкл (sec) Только для 
RGK 60 

0.5 

0.0-60.0 

P0209 MAINS/GEN interlock (sec) (Only for 
RGK 60)

 

P0210 MAINS/GEN задержка сигнала обратной связи(sec) 
Только для RGK 60 

1-60 

P0210 MAINS/GEN feedback delay (sec) (Only 
for RGK 60)

 

P0211 Переход в режим RESET при включении 

ON 

OFF/ON 

P0211 RESET mode at power-up

 

P0212 Время подачи сигнала (sec) 

OFF 

OFF/1-60 

P0212 Siren time (sec)

 

P0213 Время подачи сигнала перед вкл (sec) 

OFF 

OFF/1-60 

P0213 Siren before starting (sec) 

P0214 Время подачи сигнала при соединении с ПК(sec) 

OFF 

OFF/1-60 

P0214 Siren with PC connected (sec) 

P0215 Емкость топливного бака 

OFF 

OFF/1-30000 

P0215 Fuel tank capacity 

P0216 Контроль напряжения 

LL 

LL/LN/LL-N 

P0216 Voltage control 

P0217 Автоматический выключатель открыт (сек) 

0-600 

P0217 

Motorised circuit breaker opening (sec)

 

P0218 Автоматический выключатель закрыт (сек) 

0-600 

P0218 

Motorised circuit breaker closing (sec)

 

 

Внимание!

 Вычислительная система Только для панели управления 

рассчитана на мощность до 999 000 000 VA (999MVA). 

(1)

   Скорость вращения определяется сигналом "W" signal или датчиком 

дополнительной карты RGK X21. 

 

Caution!

 The calculation system of the devices can handle power value up to 

999 000 000 VA (999MVA). 

(1)

   Engine speed detected by the "W" signal or the "pick-up” sensor of the 

RGK X21 optional board. 

 

“03” АККУМУЛЯТОРНЫЕ БАТАРЕИ 

По

 

у мо л ч

Пределы 

“03” BATTERY 

 

 

 

 

P0301 Напряжение батареи (V) 

12 

12/24 

P0301 Battery voltage (V) 

P0302 MAX напряжение батареи (%) 

130 

110-140 

P0302 MAX voltage limit (%) 

P0303 MIN напряжение батареи (%) 

75 

60-130 

P0303 MIN voltage limit (%) 

P0304 MIN/MAX задержка напряжения(sec) 

10 

0-30 

P0304 MIN/MAX voltage delay (sec) 

 

“04” МЕНЮ ЗАПУСКА ДВИГАТЕЛЯ

 

По

 

у мо л ч

Пределы

 

“04” ENGINE STARTING

 

 

 

 

 

P0401 Напряжение на генераторе заряда стартовавшего 

двигателя (V)  

10 

OFF/3-30 

P0401 

Alternator voltage engine started (V) 

 

P0402 Напряжение на генераторе стартовавшего двигателя 
(%) 

25 

OFF/10-100 

P0402 Generator voltage engine started (%) 

P0403 Частота тока генератора стартовавшего двигателя 
(%)   

30 

OFF/10-100 

P0403 

Generator frequency engine started (%)

   

P0404 Значение “W” сигнала датчика скорости при запуске 
(% RPM)

 (1)

 

30 

OFF/10-100 

P0404 “W” signal engine started(% RPM)

 (1)

 

P0405 Время включения свеч подогрева (sec) 

OFF 

OFF/1-60 

P0405 Glow-plugs preheating (sec) 

P0406 Количество попыток пуска 

1-10 

P0406 Number of starting attempts  

P0407 Время попытки запуска (sec) 

1-30 

P0407 Starting attempt time(sec) 

P0408 Пауза между пусками(sec) 

1-30 

P0408 Pause between starting(sec) 

P0409 Пауза между прерванной и последующей попыткой 
пуска (sec) 

OFF 

OFF/1-20 

P0409 

Aborted & subsequent starting time 

      (sec)

 

P0410 Время замедления двигателя (sec) 

OFF 

OFF/1-180 

P0410 Deceleration time (sec) 

P0411 Время охлаждения двигателя (sec) 

120 

1-3600 

P0411 Cooling time (sec) 

P0412 Время удержания втягивающего реле останова 

двигателя (sec) 

OFF 

OFF/1-60 

P0412 Stop magnet time (sec) 

P0413 Задержка вкл. клапана подачи газа (sec) 

OFF 

OFF/1-10 

P0413 Gas valve delay (sec) 

P0414 Время заправки (sec) 

OFF 

OFF/1-10 

P0414 Priming time (sec) 

P0415 Время удержания возд. Заслонки (sec) 

OFF 

OFF/1-10 

P0415 Choke valve time (sec) 

P0416

 

Л

ИМИТ ВЫКЛЮЧЕНИЯ ВОЗД

.

 ЗАСЛОНКИ 

(%) 

0-100 

P0416 Choke OFF limit (%) 

Содержание RGK 50

Страница 1: ...a of the selected data page or to modify the parameters OFF RESET MAN AUT and TEST keys Press these keys to select the operating mode The illuminated LED indicates the selected operating mode if it is...

Страница 2: ...le within preset limits When the LED of the changeover symbol is on the actual closing of switching devices has occurred when flashing there is an incorrect feedback signal for the actual closing or o...

Страница 3: ...is immediately stopped if running by changing to this operating mode and any eventual alarms are reset If the cause of the alarm is still present it cannot be reset MAN mode The engine can be manuall...

Страница 4: ...release the OFF RESET key User s menu Access to parameters setting limited to those the final user needs To enter the menu press the OFF RESET key for 5 seconds then release it Commands menu Access t...

Страница 5: ...n to the screen page with data alarms measurements etc This page can contain details convenient to the user such as customer s name date of panel or genset manufacture set up file name serial number o...

Страница 6: ...ing To set the engine hour counter press the OFF RESET key and subsequently the ENTER and keys for 5s after that release them Set the counter using the or key and press the EXIT key to store and exit...

Страница 7: ...nected sec P0215 OFF OFF 1 30000 P0215 Fuel tank capacity P0216 LL LL LN LL N P0216 Voltage control P0217 1 0 600 P0217 Motorised circuit breaker opening sec P0218 1 0 600 P0218 Motorised circuit brea...

Страница 8: ...ble to check the curve characteristic by means of the set up software 06 RGK 60 06 MAINS CONTROL Only for RGK 60 0601 85 70 100 P0601 MIN voltage limit 0602 5 0 600 P0602 MIN voltage delay sec 0603 11...

Страница 9: ...by means of the set up software Caution The external CT must be chosen on the basis of the maximum current defined by the parameters P0802 and P0804 09 TEST AND MAINTENANCE 09 TEST AND MAINTENANCE 09...

Страница 10: ...GK 60 25min 0 99 P1113 Start engine delay RGK 60 only EJP 1114 RGK 60 5min 0 30 P1114 Changeover delay RGK 60 only 1115 RGK 60 OFF OFF ON P1115 Changeover block RGK 60 only P1116 OFF OFF 1 600 P1116 D...

Страница 11: ...Disabled 1 P1207 Input terminal 8 7 8 7 NO NO NC 8 7 Type of contact 8 7 0 0 0 0 6000 0 8 7 Closing delay s 8 7 0 0 0 0 6000 0 8 7 Opening delay s P1208 8 8 Disabled 1 P1208 Input terminal 8 8 8 8 NO...

Страница 12: ...lobal alarm 1 P1301 Output terminal 5 3 5 4 5 5 Function 5 3 Relay 1302 6 2 Siren 1 P1302 Output terminal 6 2 Function 6 2 Relay 1303 6 3 Decelerator 1 P1303 Output terminal 6 3 Function 6 3 Relay 130...

Страница 13: ...g RGK 60 only RGK 60 Mains motorised circuit breaker closing RGK 60 only Generator motorised circuit breaker opening Generator motorised circuit breaker closing Valve preheating 1 Relay 1 set reset vi...

Страница 14: ...inputs N B 1 See the list of the available functions in the Programmable inputs table N B Refer to the setting mode of standardinputs for the property of these inputs 15 15 PROGRAMMABLE OUTPUTS EXPANS...

Страница 15: ...efficient battery A17 X X X X X X X A1 7 Charger alternator failure A18 X X X X X A1 8 W signal failure 1 A19 W X X X X X A1 9 Low engine W speed 1 A20 W X X X X X X A2 0 High engine W speed 1 A21 X X...

Страница 16: ...erature analog sensor A47 A47 Battery charger alarm UA1 1 UA1 User s alarm 1 UA2 2 UA2 User s alarm 2 UA3 3 UA3 User s alarm 3 UA4 4 UA4 User s alarm 4 UA5 5 UA5 User s alarm 5 UA6 6 UA6 User s alarm...

Страница 17: ...age A15 A1 5 Low battery voltage A16 A1 6 Inefficient battery A17 A1 7 Charger alternator failure A18 A1 8 W signal failure 1 A19 W A1 9 Low engine W speed 1 A20 W A2 0 High engine W speed 1 A21 A2 1...

Страница 18: ...1 UA1 User s alarm 1 UA2 2 UA2 User s alarm 2 UA3 3 UA3 User s alarm 3 UA4 4 UA4 User s alarm 4 UA5 5 UA5 User s alarm 5 UA6 6 UA6 User s alarm 6 UA7 7 UA7 User s alarm 7 UA8 8 UA8 User s alarm 8 1 W...

Страница 19: ...ENERATORE CONTATTORE RETE 2 4 4 1 4 3 4 2 TA2 TA1 3 1 3 2 3 3 3 4 INGRESSI CT1 CORRENTE CT2 CURRENT INPUTS LIBERO FREE FREE FREE GENERATOR OVERLOAD GENERATOR CONTACTOR MAINS CONTACTOR REMOTE START FRE...

Страница 20: ...0 4 10 2 1 3 L1 1 1 1 2 RETE TENSIONE 2 1 1 4 N L1 2 2 2 3 GENERATORE TENSIONE 6 2 6 4 6 5 6 3 6 1 5 1 5 3 5 2 4 4 CONT GENERATORE CONTATTORE RETE 2 4 4 1 4 3 4 2 TA1 3 1 3 2 3 4 3 3 INGRESSO CORRENTE...

Страница 21: ...APRISA ALTERNATORI TIPO ELETTROVALVOLA CARBURANTE DUCATI SAPRISA ALTERNATOR TYPE BATTERY W SPEED INPUT FUEL SOLENOID VALVE BATTERIA DECELERATOR SIREN START 6 5 B 10 4 7 2 7 1 6 6 10 2 10 3 10 1 SIRENA...

Страница 22: ...typical 2 9V 5 3V t 4 3V Input high voltage 5 3V typical 4 3V 50ms Input delay 50ms W Speed input W AC Input type AC coupling 5 50Vpp Voltage range 5 50Vpp 40 2000Hz Frequency range 40 2000Hz 500rpm E...

Страница 23: ...A 12VDC 130mA 24VDC 4 1 4 2 4 3 4 4 Relay output 4 1 4 2 4 3 4 4 terminals voltage free 1 1 RGK 60 Contact type 1 NC for mains for RGK 60 only And 1 NO for generator UL B300 30VDC 1A UL Rating B300 30...

Страница 24: ...0k L N 1 2 3 Wiring mode 1 2 or 3 phases with or without neutral Current inputs Ie 5A Rated current Ie 5A 0 02 6A Measuring range 0 02 6A UL Max 5 A UL rating Supplied by an external current transform...

Страница 25: ...EN 60068 2 6 LROS Lloyd s Register Of Shipping IEC EN 60068 2 52 RINA Italian Naval Register UL 508 and CSA C22 2_N14 95 cULus IEC EN 61010 1 IEC EN 55011 EN 50082 2 IEC EN 60028 2 61 IEC EN 60068 2...

Отзывы: