![Lorentz PS1200 Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/lorentz/ps1200/ps1200_instructions-for-installation-operation-service_1939703043.webp)
43
A “multimeter” is required
and a
clamp-on
ammeter is helpful. For advice, see Section
13.7, Selecting and Using Meters for Electri-
cal Testing.
Record your test results on the Problem
Report Form,
Section 9.5.
“ Test #” REFERS TO TABLES AND PHOTOS
IN SECTION 9.6
If you see a false reading of the SOURCE
LOW or TANK FULL light
, go to
Test # 9 / 10
/ 11
Test the solar array circuit
1. OPEN-CIRCUIT VOLTAGE Section 9.6
cf. Test #1
This is “idle” voltage. It is
normally high because no current is being
drawn (it’s doing no work).
2. SHORT CIRCUIT CURRENT
cf. Test #2
or spark test — This is helpful if the pump
is trying to start or does not seem to get
full power. DISCONNECT THE ARRAY
from the controller before making this test.
(A short circuit at the array will only cause
current slightly higher than normal.) If you
don’t have a DC amp meter, a spark that
can jump 1/4" (6 mm) indicates a good
probability that the array is working
properly.
3. VOLTAGE UNDER LOAD (with pump
running)
cf. Test #3
4. CURRENT UNDER LOAD
cf. Test #4
Was power was connected to the controller
with reverse polarity?
No lights will show on the controller. This
will not cause damage. cf. Test #1
Test the motor circuit (resistance test with
POWER OFF), cf. Test #7
Make this test if there is proper voltage at the
controller input but the motor does not run. It
will confirm the condition of the entire motor
circuit, including the motor, pump cable and
splice.
Test the running current of the motor
circuit (AC amps), cf. Test #6/6A
This is one of the most useful trouble shooting
techniques because it indicates the force
(torque) that the motor is applying to the
pump. For greatest ease, use a clamp-on
ammeter, available from local electrical
equipment suppliers. It allows you to measure
current without breaking connections (cf. Test
#6A).
Table of AC RUNNING CURRENT
For
helical rotor pumps, normal running current
indicated on this table. The current stays
nearly constant as voltage and speed vary.
Your measurements may vary by as much as
10%, and more if temperature is out of the
normal range. Comparing your reading with
this table. This will indicate whether the work
load on the motor is normal for the lift it is
producing. Make note of your measurement.
Future changes may indicate pump wear, or
change in the level of the water source.
HIGHER CURRENT (especially PUMP OVER-
LOAD light) may indicate:
1. The pump may be handling excessive
sediment (sand, clay).
9.3
Electrical Testing