Finalizing the Installation
(for qualified installers only)
19
© Travis Industries
6/27/2019 - 1500
864 31K CF Aust
Gas Line Requirements
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and
NFPA 54(88), in Canada follow CSA B149.1 and the requirements listed below.
The fireplace and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPA). For pressures under
1/2 psig (kPA), isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
Fuel
This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on
the top of the gas control valve to make sure the correct fuel is used.
Gas Line Connection
Installation must be performed by a qualified installer, service agency or the gas supplier (In
Massachusetts a licensed plumber/gasfitter).
The gas inlet accepts 1/2" MPT.
Gas Inlet Pressure
Gas Pressure
Max. Input Pressure
Min. Input Pressure
Max. Manifold Pressure
Min. Manifold Pressure
Natural Gas
7" W.C. (1.74 kPA)
4.6” W.C. (1.13 kPA)
3.5” W.C. (0.87 kPA)
1.6” W.C. (0.40 kPA)
Propane
13" W.C. (3.23 kPA)
11” W.C. (2.74 kPA)
11” W.C. (2.74 kPA)
2.9” W.C. (0.72 kPA)
If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is
adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank)
should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the
regulator is at an improper pressure.