9. Heating connection

9. Heating connection

10. Electrical connection

10. Electrical connection

 

When connecting the appliance by means of a plug to a socket, pay at-
tention to the appropriate polarity (if necessary use a mains plug with 
an anti-twist protection) because the appliance must be connected in the 
proper phase!

 

An emergency power-off switch or an individual safety device is to be in-
stalled into the main distribution (for maintenance works, etc.

 

It is imperative that electrical connections regarding the appliance are to 
be carried out by a qualified professional in accordance with the applicable 
technical regulations, especially the VDE- and OVE-regulations. We do not 
accept liability for damages to the appliance as a result of inexpert connec-
tions and are subsequently excluded from warranty.

 

All electrical connecting cables leading from and to the appliance must not 
touch hot exterior surfaces of the appliance or of the chimney flue. The 
cables must not be laid over sharp edges.

 

When connecting the appliance by means of a plug to a socket, pay at-
tention to the appropriate polarity (if necessary use a mains plug with 
an anti-twist protection) because the appliance must be connected in the 
proper phase!

 

An emergency power-off switch or an individual safety device is to be in-
stalled into the main distribution (for maintenance works, etc.

 

It is imperative that electrical connections regarding the appliance are to 
be carried out by a qualified professional in accordance with the applicable 
technical regulations, especially the VDE- and OVE-regulations. We do not 
accept liability for damages to the appliance as a result of inexpert connec-
tions and are subsequently excluded from warranty.

 

All electrical connecting cables leading from and to the appliance must not 
touch hot exterior surfaces of the appliance or of the chimney flue. The 
cables must not be laid over sharp edges.

We strongly recommend the installation of a smoke detector or fire warning device 
which interrupts the current supply of the appliance in case of an emergency! Objects 
which have been left inadvertently on the cooking surface are likely to catch fire 
in case of automatic starting-up of the pellet burner (e.g. with an automatic timing 
device).

We strongly recommend the installation of a smoke detector or fire warning device 
which interrupts the current supply of the appliance in case of an emergency! Objects 
which have been left inadvertently on the cooking surface are likely to catch fire 
in case of automatic starting-up of the pellet burner (e.g. with an automatic timing 
device).

If possible the mains cable which is supplied with the appliance should be con-
nected to the power line prior to the installation of the appliance!

If possible the mains cable which is supplied with the appliance should be con-
nected to the power line prior to the installation of the appliance!

Output requirements for heating water

Heat requirement during operation must exceed 1,6 kW. If the heat output falls 
below this value, the built-in safety devices will be activated and /or the appli-
ance will be shut down.

Return flow increase

The return flow temperature must be at least 55 °C at the return flow connect

-

ing piece of the appliance (in the ideal case 60 °C), otherwise this will result in 

the building-up of soot and tar and as a consequence in corrosion.

For dimensions and detailed information on the heating connection please refer to 
the installation and operation instructions of your stove.

For dimensions and detailed information on the heating connection please refer to 
the installation and operation instructions of your stove.

 

The appliance has been exclusively designed to operate with an AC voltage 
of 230 V /50 Hz.

 

• Voltage fluctuations ranging from –15 % up to +10 % are permissible.

 

The connection is carried out by means of a 3-pole mains cable (to be sup-
plied with the appliance). 

 

Do not use sockets with power plugs without anti-twist safeguard as the ap-
pliance is dependent on the phase!

 

It is imperative that you install a protective earth conductor!

 

A 5 x 20 2,5 A T glass tube safety fuse serves as main fuse. The fuse is in-
stalled at the front wall of the built-in cupboard (inside).

 

An emergency stop switch is to be installed by the owner (for maintenance 
works, etc.).

Flue pipe connection right side:

Heating flow 1“

Heating return

 flow 1“

61

53,5

29

65*

47,5*

4,8

inlet /outlet temperature 

safety relief valve 1/2“

* for an appliance height of 85 cm!

connecting socket

*

EMERGENCY OFF

smoke/fire alarm

power line

StOvE

PEllEtS MOdulE

* … for an appliance height of 85 cm

* for an appliance height of 85 cm!

Flue pipe connection left side:

Heating flow 1“

Heating return

 flow 1“

46

53,5

29

65*

47,5*

4,8

inlet /outlet temperature 

safety relief valve 1/2“

fig. 5

fig. 6

fig. 7

Содержание LCP 70

Страница 1: ...page 1 Edition July 2010 USER MANUAL WITH INSTALLATION INSTRUCTIONS GB PELLETS MODULE P6 P7 LCP 70 LCP 75A LCP 75B Z LCP 80 Z...

Страница 2: ...12 16 Menu Top level 12 Switching on the appliance 12 Switching off the appliance 12 Setting the heating output 12 18 Main menu 13 17 Menu Settings 13 Keylock 13 Time Date 13 Automatic mode 14 Heatin...

Страница 3: ...M B8131 Closed water heating systems safety requirements NORM B8133 Safety requirements water heating systems DIN 4751 Part 1 Safety equipment for heating systems with supply temperatures up to 110 C...

Страница 4: ...existing defects and or alterations regarding the chimney and the heating system Due to low exhaust gas temperatures during changes in season it is imperative that the chimney is tight and unsuscepti...

Страница 5: ...contact shifter 12 Drive shaft rotary feeder 13 Driving chain conveying unit 14 Auger motor 15 Grate Motor 16 Flame temperature sensor 1 Cover 2 Control panel 3 Sidewall built in cupboard 4 Base pane...

Страница 6: ...y ensures that flue gases escape through the chimney The pellet stove can be operated either with wood pellets or billet wood Operation with pellets The operation with pellets is predominantly suitabl...

Страница 7: ...Wood pellets It is imperative that only wood pellets conforming to the Austrian standards NORM M7135 or DIN Plus are used Diameter 6 mm length max 30 mm Storage of wood pellets Pellets are supplied w...

Страница 8: ...bustible materials must be a maxi mum of 4 m in length and must not have too many bends To avoid condensation the air supply line must be insulated The air flue must be at least 50 or 100 mm respectiv...

Страница 9: ...tallation of a smoke detector or fire warning device which interrupts the current supply of the appliance in case of an emergency Objects which have been left inadvertently on the cooking surface are...

Страница 10: ...appliance height standard height 85 cm Fixtures which are higher f e tall cupboard have to be at least 20 cm from the pellets module away figure 9 Overhead installations Maintain a minimum distance o...

Страница 11: ...base and fas ten it at the top with both supplied screws J1 Use adjusting screws to level out unevenness of the floor and distances in height figure 15 Connections main plate Provide the connections...

Страница 12: ...and to switch from one adjustment point to the next in the ad justment levels To confirm error messages by pressing and holding the button approx 2 seconds 15 Operation Settings 15 Operation Settings...

Страница 13: ...menu press the OK button once Settings To perform appliance settings Information Display Information on the appliance and its components Default setting Detailed settings service technician 17 Menu S...

Страница 14: ...eration determines whether the appliance is operated manually standard setting OFF or whether the internal clock is used for switching the ap pliance on off The automatic operation determines whether...

Страница 15: ...text box figure 36 Press OK button once repeat the steps for the entry of the service code and enter the correct service code Press button twice to return to the top level of the menu To confirm clea...

Страница 16: ...s adjustment range of the pellet burner Boiler set point temperature WINTER 75 C Boiler set point temperature SUMMER 65 C 19 Menu Informations 19 Menu Informations To enter the menu Information from t...

Страница 17: ...rrent value ON OFF OFF Blower off Current value ON OFF OFF Motor off ON OFF OFF Ignition off ON OFF OFF Pump off only for appliances with central heating insert Press button three times to return to t...

Страница 18: ...he stove is in use temperatures up to 300 C Pay attention to the fact that these parts must not be touched when the stove is in operation Keep the firebox door closed at all times even if the stove is...

Страница 19: ...onto the grate 1 6 kg to 2 kg according to the operating instructions of the stove Close heating door Ignition of firewood manually operated The display still shows Stove OFF or Burner OFF figure 58 S...

Страница 20: ...ally at any time Objects that have been inadvertently placed on the cooking surface could ignite if the pellet burner starts up automatically e g start up according to a pre programmed time and start...

Страница 21: ...with the cleaning and or maintenance the appliance must be shut down and disconnected from the mains Emergency OFF Allow the appliance to cool down nevertheless we advise you to be careful some compon...

Страница 22: ...Ash pan can be hot fig 71 fig 72 In the event of an error message the display begins to flash Remedy the defect with the aid of the following list of defects and subsequently confirm the error messag...

Страница 23: ...en sensor short circuit Call service technician Flue gas sensor ub oven sensor failure Cause see flame sensor UB Solution see flame sensor UB F11 ignition programm after power failure power failure Pl...

Страница 24: ...litre 4 5 6 2 pellet module litre 5 8 5 8 Fuel storage container stove litre 33 2 36 5 36 5 39 8 pellet module litre kg 18 15 18 15 Fuel consumption output min max kg h 0 9 1 5 0 9 1 5 Heating period...

Страница 25: ...PE 7 PE PE 6 5 4 3 PE 1 2 3 4 9 5 PE 10 PE PE blue Earthing brown Mains connection Serial input output RS 232 Maintenance Update Fuse Micro fuse 5 x 20 mm 2 5 A T Ceramic body Control panel J1 J2 J3...

Страница 26: ...t reduce output stove on off only information only information only information scroll with UP DOWN only information scroll with UP DOWN settings from customer reset with OK brand with OK selection wi...

Страница 27: ...e in which way the defect should be repaired In the event of a repair we ensure expert performance on location or in our works This does not affect the start of warranty determined by the handover if...

Страница 28: ...KEY LOCK function OK Stove ON 13 45 Burner ON Output OK Stove ON 13 45 Burner ON Output OK Stove OFF 13 45 NO PELLETS Output OK Stove ON 13 45 Burner ON Output OK Stove ON 13 45 Burner ON Output Pres...

Отзывы: