16
Installation & Operation Manual
Air intake/vent connections
1.
Combustion Air Intake Connector
(FIG. 2-1) - Used to
provide combustion air directly to the unit from outdoors.
A fitting is provided with the unit for final connection.
Combustion air piping must be supported per guidelines
listed in the National Mechanical Code, Section 305, Table
305.4 or as local codes dictate.
2.
Vent Connector
- Used to provide a
passageway for conveying combustion gases to the
outside. A transition fitting is provided on the unit for
final connection. Vent piping must be supported per the
National Building Code, Section 305, Table 305.4 or as
local codes dictate.
DIR #2000529298 00
COMBUSTION
AIR INTAKE
CONNECTOR
Figure 2-1 Combustion Air Adapter
Vent and air piping
The Power-fin is certified as a Category II/IV boiler.
This
product has been approved for use with stainless steel vent
systems.
All venting systems used with a Power-fin boiler
must be suitable for Category IV operation except for factory
approved common vent systems operating as allowed in the
Common Venting Section on page 18.
WARNING
NOTICE
NOTICE
When a sidewall or vertical rooftop combustion air supply
system is disconnected for any reason, the air inlet pipe
must be resealed to ensure that combustion air will be free of
contaminants and supplied in proper volume.
DANGER
Failure to properly seal all joints and seams
as required in the air inlet piping may
result in flue gas recirculation, spillage
of flue products and carbon monoxide
emissions causing severe personal injury
or death.
The Power-fin uses model specific combustion air intake and
vent piping sizes as detailed in Tables 2B and 2C on page 17.
Increasing or decreasing combustion air
or vent piping to sizes not specified in this
manual is not authorized.
NOTICE
2
General
venting
Use only the materials, vent systems, and
terminations listed in Tables 2A-1 and
2A-2. DO NOT mix vent systems of
different types or manufacturers, unless
listed in this manual. Failure to comply
could result in severe personal injury,
death, or substantial property damage.
Installations must comply with applicable
national, state, and local codes. Stainless
steel vent systems must be listed as a
UL-1738 approved system for the United
States and a ULC-S636 approved system
for Canada.
Installation of a stainless steel vent system
should adhere to the stainless steel vent
manufacturer’s installation instructions
supplied with the vent system.
NOTICE
The Power-fin is supplied with an integral
FasNSeal vent connector. The installer
must use a specific vent starter adapter
supplied by the vent manufacturer to
adapt to different vent systems.
Table 2A-1 Approved Stainless Steel Vent Manufacturers
Approved Stainless Steel Vent Manufacturers
Make
Model
ProTech Systems (Dura-Vent Co.)
FasNSeal Vent
Z-Flex (Nova Flex Group)
Z-Vent
Heat Fab (Selkirk Corporation)
Saf-T Vent
Metal Fab
Corr/Guard
Securities Chimneys International
Secure Seal SS
Schebler Chimney Systems
eVent